Codes

Coding level 1

Calling up coding level 1

On weather-compensated control units, codes are
displayed as plain text.
Codes that are not assigned, due to the heating sys-
tem equipment level or the setting of other codes,
are not displayed.
Heating systems with one heating circuit without
mixer and one or two heating circuits with mixer:
Below, the heating circuit without mixer is designated
"Heating circuit 1" and the heating circuits with
mixer as "Heating circuit 2" or "Heating circuit 3".
If the heating circuits were given individual designa-
tions, the selected designation and "HC1", "HC2" or
"HC3" appear instead.
The codes are divided into groups

"General"

"Boiler"
"DHW"
"Solar"
"Heating circuit 1/2/3"
General
Coding
Coding in the delivered condition
System design
00:1
System version 1:
One heating circuit without mixer
A1 (heating circuit 1), without DHW
heating
Value, ad-
Description
dress 00: ...
2
One heating circuit without mixer A1 (heating circuit 1), with DHW heating (code is set automati-
cally)
3
One heating circuit with mixer M2 (heating circuit 2), without DHW heating
4
One heating circuit with mixer M2 (heating circuit 2), with DHW heating
5
One heating circuit without mixer A1 (heating circuit 1) and one heating circuit with mixer M2
(heating circuit 2), without DHW heating (code is set automatically)
6
One heating circuit without mixer A1 (heating circuit 1) and one heating circuit with mixer M2
(heating circuit 2), with DHW heating (code is set automatically)
7
One heating circuit with mixer M2 (heating circuit 2) and one heating circuit with mixer M3 (heat-
ing circuit 3), without DHW heating
8
One heating circuit with mixer M2 (heating circuit 2) and one heating circuit with mixer M3 (heat-
ing circuit 3), with DHW heating
40
"All codes std device"
In this group, all coding addresses from coding
level 1 (except the coding addresses of the "Solar"
group) are displayed in ascending order.
"Standard setting"
Calling up code 1
Service menu:
1. Press OK and
simultaneously for approx. 4 s.
å
2. "Coding level 1"
3. Select group of required coding address.
4. Select coding address.
5. Set the value according to the following tables and
confirm with OK.
Resetting all codes to the factory setting
Select "Standard setting".
Note
This also resets codes at coding level 2.
Possible change
00:2
For system schemes, see the follow-
to
ing table:
00:10