Heating circuit 1, heating circuit 2, heating circuit 3

Coding
Coding in the delivered condition
Economy function outdoor temperature
A5:5
With heating circuit pump logic
function (economy control): Heat-
ing circuit pump is "OFF" when the
outside temperature (OT) is 1 K
higher than the set room tempera-
ture (RT
OT
>
Parameter address A5: ...
1
2
3
4
5
6
7
to
15
Coding in the delivered condition
Extended economy function dampened outdoor temp.
A6:36
Extended economy mode disa-
bled
Extended economy function mixing valve
A7:0
Without mixer economy function
(only for heating circuits with mix-
er)
Pump idle time, transition reduced mode
A9:7
With pump idle time: heating circuit
pump "OFF" if set value is modi-
fied by changing the operating
mode or changing the set room
temperature
44
)
set
RT
+ 1 K
set
With heating circuit pump logic function: heating circuit pump "OFF"
OT
RT
+ 5 K
>
set
OT
RT
+ 4 K
>
set
OT
RT
+ 3 K
>
set
OT
RT
+ 2 K
>
set
OT
RT
+ 1 K
>
set
OT
RT
>
set
OT
RT
- 1 K
>
set
OT
RT
- 9 K
>
set
Possible change
A5:0
Without heating circuit pump logic
function
A5:1
With heating circuit pump logic func-
to
tion: heating circuit pump "OFF"
A5:15
(see the following table)
Possible change
A6:5
Extended economy mode active.
to
The burner and heating circuit pump
A6:35
will stop at a variable value, adjusta-
ble between 5 and 35 °C plus 1 °C.
Mixer is being closed. The basis for
this is the adjusted outside tempera-
ture. This is composed of the actual
outside temperature and a time con-
stant that takes account of the way
an average building cools down.
A7:1
With mixer economy function (exten-
ded heating circuit pump logic):
Heating circuit pump also "OFF":
If the mixer has been trying to
close for longer than 20 min.
Heating circuit pump "ON":
If the mixer changes to control
function
If there is a risk of frost
A9:0
Without pump idle time
A9:1
With pump idle time, adjustable from
to
1 to 15. The higher the value, the
A9:15
longer the pump idle time.