Vitodens 200-W B2HA 112, 150, 399, 530 Service

Solar

Select "Solar"
Note: The solar group is only displayed if a solar control module, type SM1, is connected.
Coding
Coding in the factory setting
Speed control solar circuit pump
02:0
DHW tank maximum temperature
08:60
Stagnation time reduction
0A:5
Flow rate solar circuit
0F:70
Extended solar control functions
20:0
Solar circuit pump is not
speed-controlled.
The solar circuit pump is
switched off when the
actual DHW tank
temperature reaches
140°F (60°C) (maximum
DHW tank temperature).
To protect the system
components and heat
transfer medium, the speed
of the solar circuit pump is
reduced when the differential
between the actual DHW
tank temperature and the set
DHW tank temperature is
less than 5 K.
Solar circuit flow rate at
the maximum pump speed
7 L/minute.
No extended control
function enabled.
Possible change
02:1
Solar circuit pump is speed-
controlled with wave packet
control.
02:2
Solar circuit pump is speed-
controlled with PWM control.
08:10
Set DHW temperature adjustable
to
from 50 to 194°F (10 to 90°C).
08:90
0A:0
Stagnation time reduction
disabled.
0A:1
Temperature differential adjustable
to
from 1 to 40 K.
0A:40
0F:1
Flow rate adjustable from
to
0.1 to 25.5 L/minute;
1 step ≙ 0.1 L/minute.
0F:255
20:1
Additional function for DHW
heating.
20:2
Differential temperature control 2.
20:3
Differential temperature control 2
and auxiliary function.
20:4
Differential temperature control 2
for central heating backup.
20:5
Thermostat function.
20:6
Thermostat function and auxiliary
function.
20:7
Solar heating via external heat
exchanger without additional
temperature sensor.
20:8
Solar heating via external heat
exchanger with additional
temperature sensor.
20:9
Solar heating of two DHW tanks.
Coding 1
43