Start Up; Tev Adjustment - Hussmann Q3SSNM6S Installation & Operation Manual

Medium temperature self contained
Table of Contents

Advertisement

s
3-6
tart up
Model
Product Application
Q3SSNM6S
Q3SSNM8S
Medium Temp. (Dairy, Deli)
Q3SSNM10S
Q3SSNM12S
1. The controller controls refrigeration tem-
perature. This is factory installed in the con-
trol panel. Adjust this control to maintain the
discharge air temperature shown. Measure
discharge air temperatures at the center of the
discharge louver.
Defrosts are time initiated and temperature
terminated for self contained. The defrost setting
is factory set as shown above.
To ensure a thorough defrost, defrost must be
terminated by the temperature termination
setting — not by time.

START UP

Follow the controller start up procedures as
detailed in Section 3 of this manual.
Each self contained merchandiser has its own
evaporator coil and a pre-set thermostatic
expansion valve (TEV). The TEV has been
factory set at design conditions to provide the
recommended performance.

TEV ADJUSTMENT

Expansion valves may be adjusted to fully feed
the evaporator. Before attempting to adjust
valves, make sure the evaporator is clear or only
lightly covered with frost, and the merchandiser
is within 10°F of its expected operating
temperature.
Adjust the valve as follows:
P/N 3086837_C
/ o
pEratIon
Discharge Air Temperature
Defrost Frequency (per day)
24°F
U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • www.hussmann.com
Type of Defrost
Temp. Termination
4
Off-cycle
a. Attach a probe to the suction line near the
expansion valve bulb.
b. Obtain a pressure reading from the factory
installed Schraeder valve. Convert the pres-
sure reading to a saturated temperature for the
refrigerant.
Temperature (b) minus Temperature (a) is the
superheat. The valve should be adjusted so that
the greatest difference between the two tem-
peratures is 3°F to 5° F.
Make adjustments of no more than
the valve stem at a time and wait for at least
15 minutes before rechecking the probe tem-
perature and making further adjustments.
Low Pressure
Cut In: 40 psi
Cut out: 10 psi
ELECTRONIC PRESSURE CONTROL
Failsafe Time (Minutes)
48°F
50
1
/