Fuses And Circuit Breakers - Trane TR150 Quick Manual

Hide thumbs Also See for TR150:
Table of Contents

Advertisement

Installation

3.2.3 Fuses and Circuit Breakers

Branch circuit protection
To prevent fire hazards, protect the branch circuits in an installation - switch gear, machines, and so on - against short
circuits and overcurrent. Follow national and local regulations.
Overcurrent protection
Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be
carried out according to local and national regulations. Circuit breakers and fuses must be designed for protection in a
circuit capable of supplying a maximum of 100000 A
UL/Non-UL compliance
To ensure compliance with UL or IEC 61800-5-1, use the circuit breakers or fuses listed in Table 3.5.
Circuit breakers must be designed for protection in a circuit capable of supplying a maximum of 10000 A
480 V maximum.
NOTICE
In the event of malfunction, failure to follow the protection recommendation may result in damage to the frequency
converter.
UL
Power [kW (hp)]
3x200–240 V IP20
0.25 (0.33)
0.37 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
Cutler-Hammer
18.5 (25)
EGE3100FFG
22 (30)
Cutler-Hammer
JGE3150FFG
30 (40)
37 (50)
Cutler-Hammer
45 (60)
JGE3200FFG
3x380–480 V IP20
0.37 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.0 (4.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
Cutler-Hammer
37 (50)
EGE3125FFG
45 (60)
BAS-SVX58D-EN
TR150 and TR170 Quick Guide
(symmetrical), 480 V maximum.
rms
Circuit breaker
Non-UL
Moeller NZMB1-
A125
Moeller NZMB1-
A160
Moeller NZMB1-
A200
Moeller NZMB1-
A125
08/2020 All rights reserved.
UL
Bussmann
Bussmann
Bussmann
Type RK5
Type RK1
Type J
FRS-R-10
KTN-R10
JKS-10
FRS-R-10
KTN-R10
JKS-10
FRS-R-10
KTN-R10
JKS-10
FRS-R-10
KTN-R10
JKS-10
FRS-R-15
KTN-R15
JKS-15
FRS-R-25
KTN-R25
JKS-25
FRS-R-50
KTN-R50
JKS-50
FRS-R-50
KTN-R50
JKS-50
FRS-R-80
KTN-R80
JKS-80
FRS-R-100
KTN-R100
JKS-100
FRS-R-100
KTN-R100
JKS-100
FRS-R-150
KTN-R150
JKS-150
FRS-R-150
KTN-R150
JKS-150
FRS-R-200
KTN-R200
JKS-200
FRS-R-200
KTN-R200
JKS-200
FRS-R-10
KTS-R10
JKS-10
FRS-R-10
KTS-R10
JKS-10
FRS-R-10
KTS-R10
JKS-10
FRS-R-15
KTS-R15
JKS-15
FRS-R-15
KTS-R15
JKS-15
FRS-R-15
KTS-R15
JKS-15
FRS-R-25
KTS-R25
JKS-25
FRS-R-25
KTS-R25
JKS-25
FRS-R-50
KTS-R50
JKS-50
FRS-R-50
KTS-R50
JKS-50
FRS-R-80
KTS-R80
JKS-80
FRS-R-80
KTS-R80
JKS-80
FRS-R-125
KTS-R125
JKS-R125
FRS-R-125
KTS-R125
JKS-R125
FRS-R-125
KTS-R125
JKS-R125
(symmetrical),
rms
Fuse
Non-UL
Bussmann
Max fuse
Type T
Type G
JJN-10
10
JJN-10
10
JJN-10
10
JJN-10
10
JJN-15
16
JJN-25
25
JJN-50
50
JJN-50
50
JJN-80
65
JJN-100
125
JJN-100
125
JJN-150
160
JJN-150
160
JJN-200
200
JJN-200
200
JJS-10
10
JJS-10
10
JJS-10
10
JJS-15
16
JJS-15
16
JJS-15
16
JJS-25
25
JJS-25
25
JJS-50
50
JJS-50
50
JJS-80
65
JJS-80
65
JJS-R125
80
JJS-R125
100
JJS-R125
125
3
3
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tr170

Table of Contents