Programming
Parameter
Parameter 1-73 Flying Start
Parameter 3-02 Minimum
Reference
4
4
Parameter 3-03 Maximum
Reference
Parameter 3-41 Ramp 1 Ramp
Up Time
Parameter 3-42 Ramp 1 Ramp
Down Time
Parameter 4-12 Motor Speed
Low Limit [Hz]
Parameter 4-14 Motor Speed
High Limit [Hz]
Parameter 4-19 Max Output
Frequency
Parameter 5-40 Function Relay
Parameter 5-40 Function Relay
Parameter 6-10 Terminal 53 Low
Voltage
Parameter 6-11 Terminal 53
High Voltage
Parameter 6-12 Terminal 53 Low
Current
Parameter 6-13 Terminal 53
High Current
Parameter 6-19 Terminal 53
mode
Parameter 30-22 Locked Rotor
Protection
Parameter 30-23 Locked Rotor
Detection Time [s]
Table 4.4 Set-up Wizard for Open-loop Applications
24
Option
Default
[0] Disabled
[0] Disabled
[1] Enabled
-4999.000–4999.000
0
-4999.000–4999.000
50
0.05–3600.00 s
Size related
0.05–3600.00 s
Size related
0.0–400.0 Hz
0 Hz
0.0–400.0 Hz
100 Hz
0.0–400.0 Hz
100 Hz
See
[9] Alarm
parameter 5-40 Function
Relay.
See
[5] Drive running
parameter 5-40 Function
Relay.
0.00–10.00 V
0.07 V
0.00–10.00 V
10 V
0.00–20.00 mA
4 mA
0.00–20.00 mA
20 mA
[0] Current
[1] Voltage
[1] Voltage
[0] Off
[0] Off
[1] On
0.05–1 s
0.10 s
08/2020 All rights reserved.
Usage
Select [1] Enabled to enable the frequency converter to
catch a motor spinning due to mains drop-out. Select [0]
Disabled if this function is not required. When this
parameter is set to [1] Enabled, parameter 1-71 Start Delay
and parameter 1-72 Start Function are not functional.
Parameter 1-73 Flying Start is active in VVC
The minimum reference is the lowest value obtainable by
summing all references.
The maximum reference is the highest value obtainable by
summing all references.
If asynchronous motor is selected, the ramp-up time is
from 0 to rated parameter 1-23 Motor Frequency. If PM
motor is selected, the ramp-up time is from 0 to
parameter 1-25 Motor Nominal Speed.
For asynchronous motors, the ramp-down time is from
rated parameter 1-23 Motor Frequency to 0. For PM motors,
the ramp-down time is from parameter 1-25 Motor Nominal
Speed to 0.
Enter the minimum limit for low speed.
Enter the maximum limit for high speed.
Enter the maximum output frequency value. If
parameter 4-19 Max Output Frequency is set lower than
parameter 4-14 Motor Speed High Limit [Hz],
parameter 4-14 Motor Speed High Limit [Hz] is set equal to
parameter 4-19 Max Output Frequency automatically.
Select the function to control output relay 1.
Select the function to control output relay 2.
Enter the voltage that corresponds to the low reference
value.
Enter the voltage that corresponds to the high reference
value.
Enter the current that corresponds to the low reference
value.
Enter the current that corresponds to the high reference
value.
Select if terminal 53 is used for current or voltage input.
+
mode only.