10 MS runtime Functions
Note
A technological area including Plant Screens cannot be set up on a PDM MS.
The monitoring cycle can and must be set up separately for each field device.
This is done in the Diagnostics View of the respective faceplate:
Figure 10-4
To change the default time of one hour, first deactivate the cyclic update, change
the cycle time, and then reactivate the cyclic update.
Available options for the cycle time:
In the lower option, the device can be assigned to one of three groups.
This can be used as selection criteria for the export functions in the overview
screen of the PDM MS.
An XML file is exported for each selected field device. The data contained can be
reused in a cloud application, for example.
PDM Maintenance Station
Entry ID: 109776936,
V1.0,
1 day,
12 hours,
1 hour,
10 minutes.
02/2020
72