4-6. MAINTENANCE MESSAGE

4-6-1. Function
When a trouble which could disturb an efficient operation of the Chiller is predicted,
it shows a notice.
4-6-2. How it is shown
It is indicated on the data display as follows.
Maintenance message
Data code
H-01
Operate purge pump
H-03
Clean cooling water tubes
H-04
Check cooling water system
H-06
Purge tank high pressure
H-07
Cooling water tubes foul
H-08
Cooling water high tem.
H-10
Power failure
★ mark : The Chiller needs an immediate action.
☆ mark : The Chiller does not need an immediate action.
However, as this might lead to ★ mark code, attention should be paid.
Consult a service agent at the next periodic maintenance.
NOTE : These indications disappear when the failure is corrected.
4-6-3. Descriptions of maintenance message and actions to be taken
Descriptions and actions by category
Maintenance Message
1 Fouling of cooling
water tubes
2 Vacuum rate
3 High temperature
of cooling water
4 Power failure
Data name
Action
Cooling water tubes must be cleaned.
Contact a service agent to do the job.
Purge indication lamp litghts at the same time
The purge tank must be purged immediately.
In case this indication is shown frequently,
contact a service agent.
Check the cooling water pump, cooling tower, etc.
See section 2-4.
4-9