Example:
If you set the Maximum Cards Per Person value to 3, then only 1000 - 100 x 3 = 700 is allowed in the Admit the last
admitted cards field for configuration.

Door configuration

In Offline Mode, all components of the door must come from the same IP-ACM v2 board.
NOTE
Door configuration in Offline Mode does not support RS-485 wiring for readers.
In Offline Mode, you must configure the readers, inputs, and outputs on the IP-ACM v2 as detailed below:
■ A reader configured on Wiegand Port 1 as the entry reader.
■ A reader configured on Wiegand Port 2 as the exit reader.
■ An input configured on Input 1 as the DSM (Door State Monitor).
■ An input configured on Input 2 as the REX (Request to Exit).
■ An output configured on Output 1 as the Door lock.
• Door configurations not complying with the above restrictions may result in unexpected operation between online and offline
NOTE
modes. However, any of the above readers, inputs, or outputs may be omitted from the door. See the following note about not
using these reader, inputs, or outputs for other purposes.
• If the readers and inputs/outputs are configured for a different purpose in C•CURE, the Offline Mode door controller uses them
for the door control function listed above, even if they are not configured for the door in C•CURE.
The door operation parameters are fixed when the IP-ACM v2 goes into offline mode and cannot be changed. The door
parameters revert to their configured settings when the IP-ACM v2 goes back online.
Offline fixed parameters:
■ Shunt time: 10 seconds
■ Unlock time: 5 seconds
■ Relock delay time: ½ second
■ Debounce time: ½ second
■ Unlock on RTE: Enabled
■ Shunt on RTE: Enabled
■ DSM shunted full shunt time: Disabled
■ Delay Relock full shunt time: Disabled
Upgrading the IP-ACM v2 Firmware
To Upgrade the IP-ACM v2 Firmware to version 04.01.00.30093 or Higher:
1. Power on the IP-ACM v2. Ensure the Ethernet cable is plugged into a port that does not require authentication.
2. Configure the IP-ACM v2 to connect to the controller.
3. Connect to the IP-ACM Status/Control web page:
a. Enter the IP address.
b. Enter the IP-ACM v2 password and click Login.
17