Configuration Jumpers - Johnson Controls S300 Series Hardware Installation Manual

Hide thumbs Also See for S300 Series:
Table of Contents

Advertisement

S300-DIN-RDR2S Module

Configuration Jumpers

The following figure illustrates the positioning of configuration jumpers for reader
power, external devices (e.g. PIR), door strike, input points, and output points.
Read the silk screen carefully to select the correct reader power.
!
Incorrect selection may result in damage to the equipment.
CAUTION
One and only one jumper is allowed for each bank.
!
CAUTION
Door Strike: Door 1
W1
DRY
+24V
W2
+12V
W3
Door Strike: Door 2
+12V
W4
+24V
W10
DRY
W11
24-10239-413 Rev. A
This document contains confidential and proprietary information of Johnson Controls, Inc.
© 2010 Johnson Controls, Inc.
External Devices: Door 1
W5
W6
+12V +24V
External Devices: Door 2
W12
W13
+12V +24V
Hardware Installation
Reader Power: Door 1
W7
W8
W9
+12V +24V +5V
Reader Power: Door 2
W14
W15
W16
+12V +5V
+24V
23