Swing Flap Motor; Main Swing Flap Motor - Daikin FTXA20A Service Manual

Split stylish r32
Table of Contents

Advertisement

2
|
Components
To install the streamer unit

2.17 Swing flap motor

2.17.1 Main swing flap motor

Checking procedures
To perform an electrical check of the swing flap motor
Service manual
138
1 Install the streamer unit in the correct location on the indoor unit.
a
a Streamer unit connector
b Streamer unit
2 Connect the streamer unit harness to the streamer unit.
Is the problem solved?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Disconnect the swing flap motor connector from the indoor unit main PCB.
2 Measure the resistance between the following pins of the motor connector.
Result: The measurements MUST be as shown in the table below.
b
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
4
"2.14 Plate
work" [
 120].
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05