3.12 Swing flap motor

3.12.1 Checking procedures

To perform an electrical check of the swing flap motor
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01D – 2022.02
a Compressor wire terminals cover
4 Install the compressor insulation.
Is the problem solved?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Disconnect the swing flap motor connector from the indoor unit main PCB.
2 Measure the resistance between the following pins of the motor connector.
Result: The measurements MUST be as shown in the table below.
Pins
1-2
1-3
1-4
1-5
2-3
2-4
2-5
3-4
3-5
4-5
a
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
"3.10 Plate
Measured resistance (Ω)
232.5~267.5
465~535
3
Components
|
4
work" [
 100].