Swing Raster Motor; Checking Procedures - Daikin FTXA20A Service Manual

Split stylish r32
Table of Contents

Advertisement

2.18 Swing raster motor

2.18.1 Checking procedures

To perform an electrical check of the swing raster motor
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
b
c
a Fan guard
b Rocker arm
c Swing raster
4 Tighten the 3 screws to fix the swing flap motor assembly.
5 Connect the harness to the swing flap motor connector.
6 Install the right side fan guard on the indoor unit (by clicking it on).
7 Install the secondary swing flap in the indoor unit (by clicking it on).
8 Install the main swing flap in the indoor unit (by clicking it on).
Is the problem solved?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Disconnect the swing raster motor connector from the indoor unit main PCB.
2 Measure the resistance between the following pins of the motor connector.
Result: The measurements MUST be as shown in the table below.
Pins
1-2
1-3
1-4
1-5
a
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
"2.14 Plate
Measured resistance (Ω)
235
2
Components
|
4
work" [
 120].
Service manual
143