Install the Vent Adapter Pipe
(Simpson Dura-Vent Components)
1. Install the Restrictor Plate: Consult Figure 8 to
determine whether the restrictor plate is needed. If so,
place the restrictor plate into the inner flue collar. (Figure
16)
2. Discard the inner starter pipe shipped with the logset.
Using the starter pipe assembly, slide the inner section
out to allow access.
• Run a bead of sealant around the bottom end of the
starter pipe and attach the assembly to the stove using
three 1/4-20 x 3/8" Phillips screws provided in the parts
bag. (Figure 20)
3. Install the Outer Adapter Pipe: Apply a 1/4" bead of
cement around the outside surface, about one inch from
the crimped end. (Figure 21) Orient the vertical seam
to the rear, and insert the crimped end of the outer pipe
into the flue collar. Fasten with three sheet metal screws
provided.
1/4-20 x 3/8
Phillips Screws
Figure 20 - Simpson DuraVent - install inner adapter pipe.
ST762
dura vent
attach inner assy
Figure 21 - Simpson DuraVent - install outer adapter pipe.
5/15/03 djt
ST763
DW dura vent
attach outer assy
15
Hearth and Home Technolgies • Oxford Direct Vent Installation Manual_R6 • 08/17
5/15/03 djt
Side Wall Termination Assembly
1. Locate the vent opening on the wall. Refer to Figure 5,
to determine the opening centerline. It may be necessary
to first position the stove and measure to find the hole
location. Depending on whether the wall is made of
combustible materials, cut the opening to the size shown
in Figure 22. Combustible wall openings must be framed
as shown in Figure 22.
Hearth & Home Technologies System
Inner Adapter
Pipe
Figure 22 - Locate vent opening
2. Measure the wall thickness and cut the wall sleeve
sections to proper length (MAXIMUM 12"). Assemble the
sleeve with the #8 sheet metal screws supplied. Attach
the firestop plate to the sleeve end with the holes. (Figure
23) NOTE: The wall sleeve is required in combustible
walls only.
3. Install the Wall Firestop/Sleeve assembly into the wall
cutout and fasten the firestop to the wall cutout framing
members. (Figure 23)
Figure 23 - Assemble the wall sleeve and firestop.
9
"
3
8
(240 mm
9
"
3
8
(240 mm
DuraVent
Combustible Wall
System
10"
(250 mm)
10"
(250 mm)
VO584-100
Vent Opening
2/99 djt
12"
(305 mm)
Max. Length
ZCS103
Zero Clearance Sleeve
& Firestop
12/6/99 djt
Framing Detail
7
"
1
2
(191 mm)
Sleeve
Firestop
3-90-693831