Performance Specifications; Input Module - Mitsubishi Electric NZ2MF2S1-32D User Manual

Cc-link ie field network basic remote i/o module
Hide thumbs Also See for NZ2MF2S1-32D:
Table of Contents

Advertisement

3.2

Performance Specifications

Input module

NZ2MFB2-16A AC input module
Item
Station type
Number of input points
Rated input voltage/rated frequency
Rated input current
Inrush current
Input voltage distortion ratio
Max. number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input impedance
Input response time
OFFON
ONOFF
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
Wiring method for common
External interface
Communication part
Module power supply part
I/O part
Applicable DIN rail
Applicable wire size
For power supply
For I/O
Applicable solderless
Terminal block for module
terminal
power supply and FG
Terminal block for input
Number of occupied stations
Reference response time
Communication cable
Module power supply
Voltage
Current
Weight
*1 Only one wire can be connected to a terminal of the terminal block for module power supply and FG. Multiple wires cannot be connected
to a terminal. Connecting two or more wires may cause a poor contact.
*2 It is recommended to use the bar solderless terminal for wiring.
NZ2MFB2-16A
Slave station
16 points
100 to 120VAC (+10%/-15%), 50/60Hz (3Hz)
8.2mA (100VAC, 60Hz), 6.8mA (100VAC, 50Hz)
200mA maximum within 1ms
Within 5%
100%
80VAC or more/5mA or more (50Hz, 60Hz)
30VAC or less/1.7mA or less (50Hz, 60Hz)
Approx. 15k (60Hz), approx. 18k (50Hz)
20ms or less (100VAC 60Hz)
1400VACrms for 1 minute between all AC external terminals and the ground
510VACrms for 1 minute between all DC external terminals and the ground
10M or higher between all AC external terminals and the ground, all DC external terminals and the
ground (500VDC insulation resistance tester)
Noise voltage: 1500Vp-p (AC type), 500Vp-p (DC type), noise width 1s, noise frequency 25 to 60Hz
(noise simulator condition)
IP1X
16 points/common (2-wire, screw terminal block type)
RJ45 connector
Terminal block for module power supply and FG (Two-piece spring clamp terminal block)
34-point one-piece terminal block
Tightening torque range for terminal screw (M3  5.2 screw): 0.59 to 0.88Nm
TH35-7.5Fe, TH35-7.5Al (compliant with IEC 60715)
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.8mm  2.0mm
Core: 0.3 to 2.0 (22 to 14 AWG)
Page 77 Applicable solderless terminal
*1
Page 80 Applicable solderless terminal
One station
1ms
An Ethernet cable that meets the 100BASE-TX standard
For details, refer to the following.
 CC-Link IE Field Network Basic Reference Manual
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
64mA or less (24VDC, all points ON)
0.31kg
*2
3 SPECIFICATIONS
3.2 Performance Specifications