NZ2MF2S1-32TE1 transistor output module
Item
Station type
Number of output points
Rated load voltage
Max. load current
Isolation method
Max. inrush current
Leakage current at OFF
Max. voltage drop at ON
Output response time
Surge suppressor
External power supply for
output part
Output type
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
Wiring method for common
Protection function
External interface
Applicable DIN rail
Applicable wire size
Applicable solderless
terminal
Number of occupied stations
Reference response time
Communication cable
Module power supply
Weight
*1 Only one wire can be connected to a terminal of the terminal block for module power supply and FG. Multiple wires cannot be connected
to a terminal. Connecting two or more wires may cause a poor contact.
*2 It is recommended to use the bar solderless terminal for wiring.
3 SPECIFICATIONS
38
3.2 Performance Specifications
NZ2MF2S1-32TE1
Slave station
32 points
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
0.1A/point, 2A/common
Photocoupler isolation
Current is limited by the overload protection function.
0.1mA or less
0.1VDC(TYP.)0.1A, 0.2VDC(MAX.)0.1A
OFFON
0.5ms or less
ONOFF
1.5ms or less (resistance load)
Zener diode
Voltage
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Current
25mA or less (TYP. 24VDC per common) External load current is not included.
Source type
500VAC for 1 minute between all DC external terminals and the ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP2X
32 points/common (two points) (1-wire, spring clamp terminal block type)
Overload protection
Limited current when detecting overcurrent: 1 to 3A/point
function
Activated to each point.
Overheat protection
Activated to two points.
function
Communication part
RJ45 connector
Module power supply part
Terminal block for module power supply and FG (Two-piece spring clamp terminal block)
I/O part
34-point two-piece spring clamp terminal block
TH35-7.5Fe, TH35-7.5Al (compliant with IEC 60715)
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.8mm  2.0mm
For power supply
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.4mm  1.5mm
For I/O
Page 77 Applicable solderless terminal
Terminal block for module
*1
power supply and FG
Page 81 Applicable solderless terminal
Terminal block for
*1
output
One station
1ms
An Ethernet cable that meets the 100BASE-TX standard
For details, refer to the following.
 CC-Link IE Field Network Basic Reference Manual
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
84mA or less (24VDC, all points ON)
0.25kg
*2
*2

Advertisement

Table of Contents
loading

Table of Contents