NZ2MFB1-32D DC input module
Item
Station type
Number of input points
Rated input voltage
Rated input current
Isolation method
Max. number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Input response time
Input type
Withstand voltage
Insulation resistance
*2
Noise immunity
Protection degree
Wiring method for common
External interface
Applicable DIN rail
Applicable wire size
Applicable solderless
terminal
Number of occupied stations
Reference response time
Communication cable
Module power supply
Weight
*1 If the input response time is set to "0ms", the actual input response time is 80s at OFF  ON, and 160s at ON  OFF.
*2 It is the noise immunity of when the input response time setting value is other than "0ms". Note that the module is easily affected by
noise if "0ms" is set.
*3 Only one wire can be connected to a terminal of the terminal block for module power supply and FG. Multiple wires cannot be connected
to a terminal. Connecting two or more wires may cause a poor contact.
*4 It is recommended to use the bar solderless terminal for wiring.
3 SPECIFICATIONS
20
3.2 Performance Specifications
NZ2MFB1-32D
Slave station
32 points
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
6.0mA TYP. (for 24VDC)
Photocoupler isolation
100%
15VDC or more/4mA or more
5VDC or less/1.7mA or less
3.8k
OFFON
0ms
(Initial setting: 10ms)
ONOFF
Positive common/negative common shared type
500VAC for 1 minute between all DC external terminals and the ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP2X
32 points/common (two points) (1-wire, screw terminal block type)
Communication part
RJ45 connector
Module power supply part
Terminal block for module power supply and FG (Two-piece spring clamp terminal block)
I/O part
34-point one-piece terminal block
Tightening torque range for terminal screw (M3  5.2 screw): 0.59 to 0.88Nm
TH35-7.5Fe, TH35-7.5Al (compliant with IEC 60715)
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.8mm  2.0mm
For power supply
For I/O
Core: 0.3 to 2.0 (22 to 14 AWG)
Page 77 Applicable solderless terminal
Terminal block for module
*3
power supply and FG
Terminal block for input
Page 80 Applicable solderless terminal
One station
1ms
An Ethernet cable that meets the 100BASE-TX standard
For details, refer to the following.
 CC-Link IE Field Network Basic Reference Manual
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
71mA or less (24VDC, all points ON)
0.30kg
*1
/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms
*4