Mitsubishi Electric NZ2MF2S1-32D User Manual page 55

Cc-link ie field network basic remote i/o module
Hide thumbs Also See for NZ2MF2S1-32D:
Table of Contents

Advertisement

NZ2MF2S1-32DTE1 DC input/transistor output module
Item
Station type
Number of input points
Rated input voltage
Rated input current
Isolation method
Max. number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Input response time
OFFON
ONOFF
Input type
Number of output points
Rated load voltage
Max. load current
Isolation method
Max. inrush current
Leakage current at OFF
Max. voltage drop at ON
Output response time
OFFON
ONOFF
Surge suppressor
External power supply for
Voltage
output part
Current
Output type
Protection function
Overload protection
function
Overheat protection
function
Wiring method for common
Withstand voltage
Insulation resistance
*2
Noise immunity
Protection degree
External interface
Communication part
Module power supply part
I/O part
Applicable DIN rail
Applicable wire size
For power supply
For I/O
Applicable solderless
Terminal block for module
terminal
power supply and FG
I/O terminal block
Number of occupied stations
Reference response time
NZ2MF2S1-32DTE1
Input specifications
Slave station
16 points
24VDC (ripple rate: 5% or less) (Allowable voltage
range: 20.4 to 28.8VDC)
6.0mA TYP. (for 24VDC)
Photocoupler isolation
100%
15VDC or more/4mA or more
5VDC or less/1.7mA or less
3.8k
*1
0ms
/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms
(Initial setting: 10ms)
Negative common type
16 points/common (1-wire, spring clamp terminal
block type)
500VAC for 1 minute between all DC external terminals and the ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP2X
RJ45 connector
Terminal block for module power supply and FG (Two-piece spring clamp terminal block)
34-point two-piece spring clamp terminal block
TH35-7.5Fe, TH35-7.5Al (compliant with IEC 60715)
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.8mm  2.0mm
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.4mm  1.5mm
Page 77 Applicable solderless terminal
*3
*3
Page 81 Applicable solderless terminal
One station
1ms
Output specifications
16 points
24VDC (ripple rate: 5% or less) (Allowable
voltage range: 20.4 to 28.8VDC)
0.1A/point, 1.6A/common
Photocoupler isolation
Current is limited by the overload protection
function.
0.1mA or less
0.1VDC(TYP.)0.1A, 0.2VDC(MAX.)0.1A
0.5ms or less
1.5ms or less (resistance load)
Zener diode
24VDC (ripple rate: 5% or less) (Allowable
voltage range: 20.4 to 28.8VDC)
20mA or less (TYP. 24VDC per common)
External load current is not included.
Source type
Limited current when detecting overcurrent: 1
to 3A/point
Activated to each point.
Activated to two points.
16 points/common (1-wire, spring clamp
terminal block type)
*4
*4
3 SPECIFICATIONS
3.2 Performance Specifications
3
53

Advertisement

Table of Contents
loading

Table of Contents