Mitsubishi Electric NZ2MF2S1-32D User Manual page 135

Cc-link ie field network basic remote i/o module
Hide thumbs Also See for NZ2MF2S1-32D:
Table of Contents

Advertisement

■Grounding the cable clamp
Use shielded cables for external wiring and ground the shields of the external wiring cables to the control panel with the
AD75CK cable clamp (manufactured by Mitsubishi Electric Corporation). (Ground the shield section 20 to 30cm away from
the module.)
(1)
20 to 30 cm
AD75CK
(1) Module
(2) Inside a control panel
For detail on AD75CK, refer to the following.
 AD75CK-type Cable Clamping Instruction Manual
■External power supply
• Use a CE-marked product for an external power supply and always ground the FG terminal. (External power supply used
for the tests conducted by Mitsubishi Electric Corporation: TDK-Lambda DRJ100-24-1, DLP-120-24-1, IDEC PS5R-SF24,
PS5R-F24)
• Use a power cable of 10m or shorter when connecting it to the module power supply terminal.
• Use a power cable of 30m or shorter when connecting it to the external power supply for output part.
(2)
(2)
Appendix 6 EMC and Low Voltage Directives
A
APPX
133

Advertisement

Table of Contents
loading

Table of Contents