EMC Directive related standards
■Emission requirements
Standard
EN61131-2: 2007
*1 QP: Quasi-peak value, Mean: Average value
*2 The module is an open type device (a device designed to be housed in other equipment) and must be installed inside a conductive
control panel. The tests were conducted with the module installed in a control panel.
■Immunity requirements
Standard
EN61131-2: 2007
*1 The module is an open type device (a device designed to be housed in other equipment) and must be installed inside a conductive
control panel. The tests were conducted with the module installed in a control panel.
*2 The accuracy of an analog-digital converter module may temporarily vary within 10%.
APPX
130
Appendix 6 EMC and Low Voltage Directives
Test item
Test details
CISPR16-2-3
Radio waves from the product are
*2
Radiated emission
measured.
CISPR16-2-1,
Noise from the product to the power
CISPR16-1-2
line is measured.
*2
Conducted emission
Test item
Test details
EN61000-4-2
Immunity test in which electrostatic
Electrostatic discharge
is applied to the cabinet of the
*1
immunity
equipment.
EN61000-4-3
Immunity test in which electric
Radiated, radio-
fields are radiated to the product.
frequency,
electromagnetic field
*1
immunity
EN61000-4-4
Immunity test in which burst noise
First transient burst
is applied to the power line and
*1
immunity
signal line.
EN61000-4-5
Immunity test in which lightning
*1
Surge immunity
surge is applied to the power line
and signal line.
EN61000-4-6
Immunity test in which high
Conducted RF
frequency noise is applied to the
*1
immunity
power line and signal line
EN61000-4-8
Immunity test in which the product
Power-frequency
is installed in inductive magnetic
*1
magnetic field immunity
field
EN61000-4-11
Immunity test in which power
Voltage dips and
supply voltage is momentarily
*1
interruption immunity
interrupted
Standard value
• 30M-230MHz QP: 40dBV/m (10m in measurement range)
• 230M-1000MHz QP: 47dBV/m (10m in measurement range)
• 150k-500kHz QP: 79dB, Mean: 66dB
• 500k-30MHz QP: 73dB, Mean: 60dB
Standard value
• 8kV Air discharge
• 4kV Contact discharge
80% AM modulation@1kHz
• 80M to 1000MHz: 10V/m
• 1.4G to 2.0GHz: 3V/m
• 2.0G to 2.7GHz: 1V/m
• AC/DC main power, I/O power, AC I/O (unshielded): 2kV
• DC I/O, analog, communication lines: 1kV
• AC power line, AC I/O power, AC I/O (unshielded): 2kV CM,
1kV DM
• DC power line, DC I/O power: 0.5kV CM, DM
• DC I/O, AC I/O (shielded), analog
CM
0.15M-80MHz,
80% AM modulation @1kHz, 10Vrms
50Hz/60Hz, 30A/m
• 0%, 0.5 periods, starting at zero-crossing
• 0%, 250/300 cycles (50/60Hz)
• 40%, 10/12 cycles (50/60Hz)
• 70%, 25/30 cycles (50/60Hz)
*1
*1
*2
, communication lines: 1kV