Toshiba MMC-AP0157HP1-E Service Manual page 52

Multi type
Table of Contents

Advertisement

Target outdoor unit (SMMS-i – Series 4)
CODE No.
Indoor unit
00
data *2
01
02
03
04
05
06
08
09
FA
System unit
0A
data
0B
0C
0D
CODE No.
U1 U2 U3 U4
Individual
10 20 30 40
data 1 of
outdoor
11 21 31 41
unit *3
12 22 32 42
13 23 33 43
14 24 34 —
15
25
35
45
16
26
36
46
17
27
37
18
28
38
48
19
29
39
49
1A
2A
3A
4A
1B
2B
3B
1C
2C
3C
4C
1D
2D
3D
4D
1E
2E
3E
1F
2F
3F
4F
*1 The TF/TSA/TOA sensors are equipped only with some types of indoor units. The data does not appear for
other types.
*2 In the case of group connection, only the header indoor unit data can be displayed.
*3 The upper digit of CODE No. indicates the outdoor unit No.
*4 [(The upper digit of CODE No.) – 4] indicates the outdoor unit No.
1
, 5
... U1 outdoor unit (Header unit)
2
, 6
... U2 outdoor unit (follower unit 1)
3
, 7
... U3 outdoor unit (follower unit 2)
4
, 8
... U4 outdoor unit (follower unit 3)
*5 Only CODE No. 5 of U1 outdoor unit (Header unit) is displayed.
Data
Room temperature (in control)
Room temperature (Remote controller)
Air Temperature (TA)
Coil Temperature (TCJ)
Coil Temperature (TC2)
Coil Temperature (TC1)
Discharge temperature (TF) *1
PMV
Air Suction Temperature of direct expansion
coil (TSA) *1
Outdoor Air Temperature (TOA) *1
Number of connected indoor units
Total horse power of connected indoor units
Number of connected outdoor units
Total horse power of outdoor units
Data
Detection pressure of high-pressure sensor
(Pd)
Detection pressure of low-pressure sensor
(Ps)
Discharge temperature of compressor 1
(Td1)
Discharge temperature of compressor 2
(Td2)
Discharge temperature of compressor 3
(Td3)
Suction Temperature (TS)
Coil Temperature 1 (TE1)
Coil Temperature 2 (TE2)
Liquid Temperature (TL)
Outdoor Temperature (TO)
PMV1 + 2
PMV4
Current of compressor 1 (I1)
Current of compressor 2 (I2)
Current of compressor 3 (I3)
Outdoor fan current (IFan)
Format
Unit
x1
˚C
x1
˚C
x1
˚C
x1
˚C
x1
˚C
x1
˚C
˚C
x1
x1/10
pls
x1
˚C
x1
˚C
x1
x10
HP
x1
x10
HP
Format
Unit
MPa
x100
MPa
x100
˚C
x1
x1
˚C
x1
˚C
x1
˚C
x1
˚C
˚C
x1
˚C
x1
x1
˚C
x1
pls
pls
x1
A
x10
A
x10
x10
A
A
x10
– 52 –
FILE NO. SVM-16042
Remote controller display example
[0024]=24 ˚C
[0150]=1500 pls
[0024]=24 ˚ C
[0048]=48
[0415]=41.5HP
[0004]=4
[0420]=42HP
Remote controller display example
[0123]=1.23 MPa
[0024]=24 ˚C
[0050]=500 pls
[0135]=13.5 A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmc-ap0187hp1-eMmc-ap0247hp1-eMmc-ap0277hp1-eMmc-ap0367hp1-eMmc-ap0487hp1-eMmc-ap0567hp1-e ... Show all

Table of Contents