Address setup (Manual setting from remote controller)
In case that addresses of the indoor units will be
determined prior to piping work after cabling work
Set an indoor unit per a remote controller.
Turn on power supply.
1
SET
CL
TEST
Push
+
+
for 4 seconds or more.
2
(Line address)
Using the temperature setup
buttons, set
to the CODE No.
3
Using timer time
set the line address.
4
SET
Push
button. (OK when display goes on.)
5
(Indoor unit address)
Using the temperature setup
buttons, set
to the CODE No.
6
Using timer time
set 1 to the line address.
7
SET
Push
button. (OK when display goes on.)
8
(Group address)
Using the temperature setup
buttons, set
to the CODE No.
9
Using timer time
set
to Individual,
Master unit and
10
SET
Push
button.
(OK when display goes on.)
11
TEST
Push
button.
Setup completes.
(The status returns to the usual stop status.)
Note 1)
When setting the line address from the remote controller, do not use Address 29 and 30.
As they are addresses which cannot be set to the outdoor unit, if they are set, the check code [E04] (Indoor/Outdoor
communication circuit error) is issued.
Note 2)
When an address was manually set from the remote controller and the central control over the refrigerant lines is
carried out, perform the following setting for the Master unit of each line.
Set the line address for every line using SW13 and 14 on the interface P .C. board of the center unit in each line.
Except the least line address No., turn off SW30-2 on the interface P .C. board of the Master units in the lines
connected to the identical central control.
(Draw the terminal resistances of indoor/outdoor and central control line wirings together.)
For each refrigerant line, connect the relay connector between Master unit [U1U2] and [U3U4] terminals.
After then set the central control address.
(For setting of the central control address, refer to the Installation manual for the central control equipment.)
buttons simultaneously
/
/
buttons,
/
/
buttons,
/
/
buttons,
to
to sub unit.
(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)
Outdoor
Indoor
Line address
1
Indoor unit address
1
Group address
1
Header unit
For the above example, perform setting by connecting singly the
wired remote controller without remote controller inter-unit cable.
Group address
TEMP.
2, 5, 8
11
END
FILTER
RESET
TEST
1
<Operation procedure>
1
2
7
8
– 44 –
FILE NO. SVM-16042
Outdoor
Indoor
Indoor
Indoor
1
1
2
3
2
2
Follower
unit
Individual
: 0000
Header unit : 0001
In case of group control
Follower unit : 0002
ON / OFF
3, 6, 9
TIMER SET
FAN
MODE
TIME
SAVE
VENT
4, 7, 10
SET
CL
SWING/FIX
UNIT LOUVER
3
4
5
9
10
11
Indoor
2
2
1
2
2
2
6
END