Toshiba MMC-AP0157HP1-E Service Manual page 35

Multi type
Table of Contents

Advertisement

In case of wireless remote controller
1. When TEMPORARY button is pushed for 10 seconds or more, "Pi!" sound is heard and the operation
changes to a forced cooling operation. After approx. 3 minutes, a cooling operation starts forcedly.
Check cool air starts blowing. If the operation does not start, check wiring again.
2. To stop a test operation, push TEMPORARY button once again (Approx. 1 second).
Check wiring / piping of the indoor and outdoor units in forced cooling operation.
TEMPORARY button
– 35 –