Toshiba MMC-AP0157HP1-E Service Manual page 24

Multi type
Table of Contents

Advertisement

No.
Item
6
Air speed selection
(Continued):
7
Prevention of cold air
discharge
Outline of specifications
Standard
CODE No.
[5d]
SW501 (1)/(2)
OFF/OFF
Tap
COOL
F1
F2
F3
F4
F5
F6
HH
F7
H+
F8
F9
H
FA
FB
L+
FC
L
FD
3) In heating operation, the mode changes to [LL] if thermostat is turned off.
1. In heating operation, the higher temperature of
TC2 sensor and TCJ sensor is compared with
temperature of TC1 sensor and then the lower
temperature is used to set the upper limit of the
fan tap.
When B zone has continued for 6 minutes,
the operation shifts to C zone.
In defrost time, the control point is set to
+6°C.
(°C)
32
D
30
C
28
26
20
16
– 24 –
Type 1
0000
0001
ON/OFF
HEAT
COOL
HH
H+
HH
H
H+
H
L+
L+
L
L
LL
A zone: OFF
B zone:
Over 26°C, below 28°C, ULTRA LOW (LL)
C zone:
E
Over 28°C, below 30°C, LOW (L)
D zone:
Over 30°C, below 32°C, MED (H)
E zone: HIGH (HH)
B
A
FILE NO. SVM-16042
Remarks
Selection of high ceiling
type CODE No. :
[5d] or selection of high
ceiling on P .C. board SW501
Type 3
0003
OFF/ON
HEAT
COOL
HEAT
HH
HH
HH
H+
H+, H
H+, H
H
L+
L+
L
L
L+
L
LL
LL
TCJ: Temperature of indoor
heat exchanger sensor
In D and E zones, priority
is given to remote control-
ler air speed setup.
In A zone "
" is displayed.