[BFM #24] Baud Rate

Set the baud rate in this BFM. The current baud rate can be found in BFM #37.
Note
• The Baud Rate must be equal for all nodes in the network.
• The new value needs to be stored by BFM #22 and the Module has to be restarted to make the new setting
effective.
BFM Value
K10
K20
K50
K100
K125
K250
K500
K800
K1000
Other value
6.8

[BFM #25] Communication Status

Displays the FX
Note
• A change of the function mode, the baud rate, or Node ID requires a restart of the FX
effective.
• If a configuration BFM is written to while in online mode (BFM #25 bit 4 is ON), BFM #29 bit 5 will be set
ON.
• When BFM #25 bit 7 is ON, the Module is initializing the internal data structures and the BFM, and any TO
command (write access) prohibited. If the BFM is written to, BFM #29 bit 5 will be set to ON.
When BFM #25 bit 7 is bit ON, the only access allowed is to read (FROM) BFM #25 and BFM #29.
Module restart
When restarting the module, set BFM #25 Bit 0 to ON.
In this case, set data that was not saved will be lost.
Bit
Module online/offline
Layer 2 modes:
OFF:
ON:
Bit 0
CANopen
OFF:
ON:
OFF:
Bit 1
ON:
Bit 2, 3
Reserved
114
Baud Rate 10kbps
Baud Rate 20kbps
Baud Rate 50kbps
Baud Rate 100kbps
Baud Rate 125kbps
Baud Rate 250kbps
Baud Rate 500kbps
Baud Rate 800kbps
Baud Rate 1000kbps
Setting prohibited
If an invalid baud rate is written to BFM #24, the BFM will keep its former value and BFM #29 bit 11 will be set.
-CAN communication status.
3U
FROM (Read Access)
Offline
Online
®
modes:
Not in Operational State
Operational State
The error counter is below the warning level, in error
passive or in bus-off.
The error counter of the CAN controller has reached
the warning level.
→ Refer to and Section 6.13 and 6.14
Description
Description
TO (Write Access)
Module restart
A restart is necessary to activate a new setting of the function
mode (BFM #21), the baud rate (BFM #24), the Node-Id
(BFM #27) or to activate the NMT master setting.
All not saved settings will be lost.
OFF:
Normal operation
ON:
Restart module
Reserved
6 Allocation of Buffer Memories
6.7 [BFM #24] Baud Rate
-CAN to become
3U
→ Refer to Subsection 5.8.5 and
Section 6.5, 6.7 and 6.10