Enter the reading that is to correspond to a 4 mA output. Units are defined in Sensor units for
Level, Space, or Distance.
4 mA setpoint can be set less than 0 m, and 20 mA setpoint can be set greater than 30 m when
1)
using handheld programmer. Recommended range is 0 to 30 m.
8.5.42
20 mA Setpoint (2.3.1.4.)
Sets the process level corresponding to the 20 mA value. 20 mA always defaults to 100%, and
mA Output Function determines whether this is a Level, Space, or Distance measurement.
Level and Space are measured as a percentage of the difference between High Calibration
Point and Low Calibration Point: Distance is measured as a percentage of Low Calibration
Point.
Enter the reading that is to correspond to a 4 mA output. Units are defined in Sensor units for
Level, Space, or Distance.
4 mA setpoint can be set less than 0 m, and 20 mA setpoint can be set greater than 30 m when
1)
using handheld programmer. Recommended range is 0 to 30 m.
8.5.43
Minimum mA limit (MIN. mA LIMIT) (2.3.1.5.)
Prevents the mA output from dropping below this minimum level for a measurement value. This
does not restrict the Fail-safe or manual settings.
8.5.44
Maximum mA limit (MAX. mA LIMIT) (2.3.1.6.)
Prevents the mA output from rising above this maximum level for a measurement value. This
does not restrict the Fail-safe or manual settings.
SITRANS LR260 with mA/HART
Operating Instructions, 11/2019, A5E32337683-AD
1)
Values
Related Parameters
Values
Values
Range: 0 to 30 m
1)
Default: 30 m (set to value corresponding to 100% as defined by mA
Output Function)
mA Output Function
Range: 3.8 to 20.5 (mA)
Default: 3.8 (mA)
Range: 3.8 to 20.5 (mA)
Default: 20.5 (mA)
Parameter reference
8.5 Setup (2.)
93