5-2. Error Flowchart
Station Number(UNIT NO.) Setting Error Flowchart
The ERROR 2 LED
flashes.
Is the station number(UNIT NO.)
set in the range of 01 to 32?
Set the station number(UNIT NO.)
in theproper range(01 to 32).
* Be sure to set it not to overlap
with other station in the same
network.
Turn OFF tthe power.
Then, turn it ON again.
Has the ERROR 2 LED
turned OFF?
END
64
YES
NO
NO
YES
Is the unit set for PC
Link Mode?
YES
Is the station number(UNIT NO.)
set in the range of 01 to 16?
NO
Set the station number(UNIT NO.)
in the proper range(01 to 16).
* Be sure to set it not to overlap
with other station in the same
network.
Please contact us.
Replace the unit with a spare W
Type(Wire) Link Unit if available.
NO
YES