2.2 Input Unit Specifications
■
Terminal layout
The COM terminals are connected internally.
2.2.3 64-point-type DC Input Unit
■
Description
Items
Insulation system
Rated input voltage
Rated input current
Input impedance
Operating voltage range
Min. ON voltage/Min. ON current
Max. OFF voltage/Max. OFF current
Response time
Input points per common
Operating mode indicator
External connection method
Weight (unit)
2-6
AFP7X64D2
Optical coupler
24V DC
Approx. 2.7 mA (at 24 V DC)
Approx. 8.2kΩ
20.4 to 26.4 V DC
19.2 V/2.5 mA
5 V/1.5 mA
OFF→ON
0.2 ms max. (changeable with constant switching function at time of
input)
ON→OFF
0.2 ms max. (changeable with constant switching function at time of
input)
32 points/common
32-point LED indicator (Lit in ON state)
Connector connections (40P, conforming to MIL standards)
Approx. 110g
WUME-FP7DIO-05