PLC Link

4.3 Setting Items for PLC Link

4.3.1 Station No. Setting

 In the PLC link where multiple PLCs are connected to the transmission line, station no.
should be set to identify each PLC.
 Station nos. are the numbers to identify the different PLCs on the same network. The same
number must not be used for more than one PLC on the same network.

4.3.2 Max. Station No. Setting

 Set the Max. station no. for PLC to be connected to the PLC link.
 The smaller the Max. station no. is, the shorter the relative transmission time becomes.
NOTES
Station nos. should be set sequentially and consecutively, starting from 1,
with no breaks between them. If there is a missing station no., the
transmission time will be longer.
Set the same value for the Max. station no. for all PLCs connected to the
same PLC link.
4-6