Number
Description
Remote I/O Operating Mode Setting
35
Confirmation for connection of a slave station
36
Selection of Remote I/O update method
Setting for P/W Link 0
40
Link data register memory size
42
Link relay send
43
memory size
44
Link data register
45
send memory size No.r of words to be sent
46 to 49
Unused
Setting for P/W PL Link 1
50
Link relay memory size
51
Link data register memory size
52
Link relay send
53
memory size
54
Link data register
55
send memory size No. of words to be sent
59 to 59
Unused
Notes :
1. The total maximum memory available for the sequence program area size and machine language
program area size is 10K words for the FP3.
2. The value of address No.5 and 6 must be the same. The Set(Preset) value area(SV) and the
Count(Elapsed) value area(EV) are also Hold/Non-hold according to the set value of No.6.
3. Each holding area is divided by the word number you use. The area from 0 to the number specified
is Non-hold, and from that number to the end is Hold. To set the whole area hold operation, use a
number which is 1 word larger than the maximum.
4. Set addresses No.30 to 32 as.shown below.
Set time = Set value x 2.5ms(Set value is decimal.)
The default value are set as shown below.
Address No.30...default value: 120(set time: 300 ms)
Address No.31...default value:2,600(set time: 6.5 s)
Address No.32...default value: 800(set time: 2.0 s)
5. Set the address No.33 as below.
Set time=Set value x 2.0 µs(Set value is decimal.)
The default value: 5,000(set time:10 ms)
6. The terms "Hold" and "Non-hold" are specified as;
* Hold area: the memory area whose contents will be lost or modified if the operating power is lost.
* Non-hold area: the memory area whose contents will be lost or modified if the operating power is
lost.
82
Starting words No.
No. of words to be sent
Starting words No.
Starting words No.
No. of words to be sent
Starting words No.
Default value
Settable range
1(Set)
0:Release
1:Set
0
0:Synchronous
1:Asynchronous
0
0 to 128 words
(0 to 1,024 points)
0
0 to 63
0
0 to 64 words
0
0 to 127
0
0 to 127 words
0
0 to 64 words
(0 to 1,024 points)
0
0 to 128 words
64
64 to 127
0
0 to 64 words
128
128 to 255
0
0 to 127 words