Electrical Specifications - Delta DVP-SS2 Instruction Sheet

Hide thumbs Also See for DVP-SS2:
Table of Contents

Advertisement

B. DVP28SS2
9
1 0
1. Model type
2. POWER, RUN, ERROR, COM1 and COM2
status indicator
3. I/O terminals
4. I/O point indicator
5. I/O port for program communication (RS-232)
6. RUN/STOP switch
7. DIN rail clip
 Electrical Specifications
DVP
Model
Item
Power supply voltage
Inrush current
Fuse capacity
Power consumption
Power protection
Operation
environment
Installation position
Pollution rating
Protection rating
Over voltage
tolerance limit
Insulation resistance
Noise immunity
Grounding
Operation / storage
Vibration / shock
resistance
Atmospheric
pressure
Weight (g)
1
2
3
4
5
6
7
8
14SS211R
24VDC (-15% ~ 20%)
(with counter-connection protection on the polarity of DC input power)
DVPPS01(PS02): input 100-240VAC, output 24VDC/1A(PS02: 2A)
1.8W
With counter-connection protection on the polarity of DC input power
Free of corrosive gas
Inside the control box
2
IP20
1,500VAC (Primary-secondary), 1,500VAC (Primary-PE),
500VAC (Secondary-PE)
> 5MΩ (all I/O point-to-ground: 500VDC)
ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV,
Analog & Communication I/O: 1kV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
The diameter of grounding wire cannot be smaller than the wire
diameter of terminals L and N (All DVP units should be grounded
directly to the ground pole).
Operation: 0°C ~ 55°C (temp.), 5 ~ 95% (humidity), no condensation.
Storage: -25°C ~ 70°C (temp.), 5 ~ 95% (humidity), no condensation.
International standards: IEC61131-2, IEC 68-2-6 (TEST
Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Operation: 1080 ~ 795hPa (Equivalent to -1000 ~ 2000 feet above sea
level)
Storage: 1080 ~ 660hPa (Equivalent to -1000 ~ 3500 feet above sea
level)
97g
46. 00
10. DC power input
11. Extension unit clip
12. Extension port
13. DIN rail mounting slot (35mm)
14SS211T
12SS211S
Max. 7.5A@24VDC
1.85A/30VDC, Polyswitch
1.5W
82.5g
90g
- 2 -
6 8.80
6 0.0 0
8. RS-485 communication port
9. Nameplate
28SS211R
3.6W
177g
11
1 2
1 3
28SS211T
28SS211S
1.7W
155g(T)/
151g(S)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvp ss2 seriesDvp14ss211rDvp14ss211tDvp12ss211sDvp28ss211rDvp28ss211t ... Show all

Table of Contents