Thank you for choosing Delta's DVP-EX2 series PLC. DVP-EX2 series provides 30
points MPU (16 points digital Input, 10 points digital Output, 3 channel Analog input and
1 channel Analog output). The maximum I/O points including those on the MPU are 256
points. DVP-EX2 series PLCs satisfy various applications in that they can be used with
analog input/output modules. Users do not have to install any batteries in DVP-EX2
series PLCs. The PLC programs and the latched data are stored in the high-speed flash
memories.
This instruction sheet provides only information on the electrical specification,
general functions, installation and wiring. For detailed program design and applicable
instructions for DVP-EX2, please refer to "DVP-EX2 Operation Manual:
Programming". For details on the optional peripheral, please refer to the instruction
sheet enclosed in the package.
DVP-EX2 series PLC is an OPEN TYPE device and therefore should be installed in
an enclosure free of airborne dust, humidity, electric shock and vibration. The
enclosure should prevent non-maintenance staff from operating the device (e.g. key
or specific tools are required for operating the enclosure) in case danger and damage
on the device may occur.
DO NOT connect the input AC power supply to any of the I/O terminals; otherwise
serious damage may occur. Check all the wiring again before switching on the power.
Make sure the ground terminal
electromagnetic interference.
Product Profile & Dimension
POW ER, RU N ERROR
I/O term inal No.
R un/Stop sw itch
COM 1 C om munica tion
port
(RS -232 C)
I/O term inal No.
M odel Nam e
C OM 2/COM 3 (R S-485)
DIN rail clip

Electrical Specifications

Model
Item
Power supply
voltage
Connector
Operation
Power supply fuse
Power consumption
,
& C OM
indicators
DVP30E X2
16 DI /10 DO/ 3A I/ 1AO
157
165
DVP30EX200R
100 ~ 240VAC (-15% ~ 10%)
European standard removable terminal block (Pin pitch: 5mm)
DVP-EX2 starts to run when the power rises to 95 ~ 100VAC and stops
when the power drops to 70VAC. If the power is suddenly cut off, the
MPU will continue running for 10ms.
ENGLISH
...........................................................................
is correctly grounded in order to prevent
2A/250VAC
30VA
- 1 -
I/O p oint indica tors
I/O m odule
conn ection
O utput type
R
M ounting slot
(35m m)
I/O m odule clip
Direct m oun ting hole
Rem ovable I/O term ina l block
[ Figure 1 ]
Unit: mm
61.5
78
[ Figure 2 ]
DVP30EX200T
,
50/60Hz ±5%
port

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvp30ex200rDvp30ex200t

Table of Contents