Table 8A Cooling Pressure - Standard Airflow; Table 8B Cooling Pressure - Balanced Climate Airflow - Bard Q36A4DA Installation Instructions Manual

11eer q-tectm q**a4d series packaged air conditioner
Hide thumbs Also See for Q36A4DA:
Table of Contents

Advertisement

Return Air Temp
Model
(DB/WB)
75/62
Q36A4D
80/67
85/72
75/62
Q42A4D
80/67
85/72
75/62
Q48A4D
80/67
85/72
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Return Air Temp
Model
(DB/WB)
75/62
Q36A4D
80/67
85/72
75/62
Q42A4D
80/67
85/72
75/62
Q48A4D
80/67
85/72
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in
the system, the charge should be removed and system evacuated and recharged to serial plate charge weight.
NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check condenser fan
wiring. See Condenser Fan Operation on page 28.
Manual 2100-752B
Page
36 of 49
TABLE 8A
Cooling Pressure – Standard Airflow
Pressure
75
80
Low Side
127
128
High Side
321
340
Low Side
136
137
High Side
329
349
Low Side
141
141
High Side
341
361
Low Side
129
130
High Side
338
359
Low Side
138
139
High Side
347
369
Low Side
142
143
High Side
359
381
Low Side
123
125
High Side
337
357
Low Side
132
134
High Side
346
367
Low Side
137
138
High Side
358
379
TABLE 8B
Cooling Pressure – Balanced Climate Airflow
Pressure
75
80
Low Side
115
116
High Side
311
332
Low Side
123
125
High Side
319
340
Low Side
128
129
High Side
330
352
Low Side
115
119
High Side
327
351
Low Side
123
127
High Side
336
360
Low Side
127
131
High Side
347
372
Low Side
115
116
High Side
328
348
Low Side
123
124
High Side
336
357
Low Side
127
128
High Side
348
370
Air Temperature Entering Outdoor Coil °F
85
90
95
100
128
129
130
132
361
384
408
434
137
138
140
141
371
394
419
445
142
143
144
146
384
408
433
461
131
132
133
134
382
405
429
454
140
141
142
143
391
415
440
466
145
146
147
148
405
430
455
482
126
128
129
130
379
401
424
449
135
137
138
140
388
411
435
460
140
141
143
144
402
425
450
476
Air Temperature Entering Outdoor Coil °F
85
90
95
100
118
119
120
122
353
375
399
423
126
127
129
130
362
385
409
434
130
132
133
135
375
398
423
449
122
125
128
130
375
399
424
450
131
134
137
139
384
409
435
461
135
139
141
144
398
424
450
477
117
118
119
121
370
392
416
441
125
126
128
129
379
402
427
452
129
131
132
134
392
416
441
468
105
110
115
120
133
135
137
138
461
490
521
554
143
144
146
149
473
503
535
568
148
149
152
154
490
521
553
588
135
137
138
140
480
508
536
565
145
146
148
149
493
521
549
579
150
151
153
155
510
539
569
600
132
133
135
136
474
501
529
558
141
143
144
146
487
514
543
573
146
148
149
151
504
532
562
593
105
110
115
120
123
125
127
128
449
476
503
532
132
134
135
137
460
488
516
546
137
138
140
142
477
505
534
565
131
133
133
133
476
503
530
558
140
142
142
143
488
516
544
572
145
147
147
148
505
534
563
592
122
124
126
127
466
493
521
550
131
132
134
136
478
506
534
564
135
137
139
141
495
523
553
484
125
141
587
151
603
156
624
141
595
151
610
156
631
137
588
147
604
152
625
125
130
562
139
576
144
596
133
587
143
602
148
623
130
580
139
595
143
615

Advertisement

Table of Contents
loading

Table of Contents