Q48A4D Cooling And Dehumidification Application Data - Bard Q36A4DA Installation Instructions Manual

11eer q-tectm q**a4d series packaged air conditioner
Hide thumbs Also See for Q36A4DA:
Table of Contents

Advertisement

Q48A4D Cooling and Dehumidification Application Data

OD Temp.
DB/WB
2
Mode
Total Cooling Btuh
Sensible Btuh
Latent Btuh
075/64.1
Lbs. H20/hr.
(55% RH)
Supply Air DB
Supply Air WB
Suction PSIG
Discharge PSIG
Total Cooling Btuh
Sensible Btuh
Latent Btuh
75/65.5
Lbs. H20/hr.
(60% RH)
Supply Air DB
Supply Air WB
Suction PSIG
Discharge PSIG
Total Cooling Btuh
Sensible Btuh
Latent Btuh
75/66.7
Lbs. H20/hr.
(65% RH)
Supply Air DB
Supply Air WB
Suction PSIG
Discharge PSIG
Values listed are with ventilation package disabled
1
Return air temperature °F @ Default airflow (1300 CFM) for AC tests and Balanced Climate airflow (910 CFM) for
2
dehumidification tests
Suction pressure +/- 4 psi, Discharge pressure +/- 10 psi
3
Manual 2100-752B
Page
48 of 49
75°F
A/C
49,500
34,200
S/T
0.691
15,300
14.4
54.7
53.1
127
3
339
3
50,300
32,200
S/T
0.640
18,100
17.1
56
54.5
129
3
341
3
51,300
30,200
S/T
0.589
21,100
19.9
57.3
56
132
3
344
3
1
85°F
Dehum
A/C
17,800
46,700
3,900
32,800
0.219
0.702
13,900
13,900
13.1
13.1
71.9
55.6
58.7
53.8
116
129
292
382
20,200
47,700
3,500
30,700
0.173
0.644
16,700
17,000
15.8
16
72.4
56.9
59.6
55.3
119
132
296
384
21,500
48,600
2,400
28,700
0.112
0.591
19,100
19,900
18
18.8
73.5
58.1
60.7
56.8
122
134
300
387
95°F
Dehum
A/C
13,700
43,600
1,100
31,200
0.080
0.716
12,600
12,400
11.9
11.7
74.5
56.5
60.1
54.5
119
130
323
428
15,100
44,600
0
29,100
0.000
0.652
15,100
15,500
14.2
14.6
75.6
57.8
61.3
56
122
133
326
430
16,500
45,600
-1,200
27,100
0
0.594
17,700
18,500
16.7
17.5
76.6
59.1
62.4
57.5
125
136
330
433
Dehum
8,000
-3,200
0
11,200
10.6
78.2
61.9
121
354
9,300
-4,400
0
13,700
12.9
79.3
63.1
124
357
10,700
-5,500
0
16,200
15.3
80.3
64.2
127
361

Advertisement