Table 3 Co; Table 6 Cooling Pressure - Standard Airflow; Table 7 Cooling Pressure - Balanced Climate - Bard 11EER WA Series Installation Instructions Manual

Wall mount air conditioner
Table of Contents

Advertisement

Return Air Temp
Model
(DB/WB)
75/62
W12AB
80/67
85/72
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge
being in the system, the charge should be removed and system evacuated and recharged to serial plate charge weight.
NOTE:
Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check
condenser fan wiring. See "Condenser Fan Operation".
* Operating at these conditions would be outside the compressor operating envelope and is not recommended.
Return Air Temp
Model
(DB/WB)
75/62
W12AB
80/67
85/72
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Tables are based upon Balanced Climate CFM (airflow) across the evaporator coil. If there is any doubt as to correct
operating charge being in the system, the charge should be removed and system evacuated and recharged to serial plate
charge weight.
NOTE:
Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check
condenser fan wiring. See "Condenser Fan Operation".
* Operating at these conditions would be outside the compressor operating envelope and is not recommended.
Manual 2100-715B
Page
22 of 25
TABLE 6
Cooling Pressure – Standard Airflow
Pressure
75
80
85
Low Side
126
129
131
High Side
292
313
335
Low Side
135
137
140
High Side
299
321
343
Low Side
140
142
145
High Side
310
332
355
TABLE 7
Cooling Pressure – Balanced Climate Airflow
Pressure
75
80
85
Low Side
120
122
124
High Side
285
306
328
Low Side
128
131
133
High Side
293
314
336
Low Side
133
135
138
High Side
303
325
348
Air Temperature Entering Outdoor Coil °F
90
95
100
105
110
133
136
138
140
143
357
381
404
429
454
143
145
148
150
152
367
390
415
440
466
148
150
153
155
158
379
404
429
455
482
Air Temperature Entering Outdoor Coil °F
90
95
100
105
110
127
129
132
134
136
350
373
397
422
447
136
138
141
143
146
359
383
407
432
458
140
143
146
148
151
372
396
422
448
474
115
120
125
131
145
147
149
152
480
507
534
568
155
157
160
--*
492
520
548
160
153
165
--*
510
538
567
115
120
125
131
139
141
143
146
473
500
527
561
148
151
153
--*
485
513
541
153
156
159
--*
502
531
560