Table 9 Electrical Specifications Q**A4D Series - Bard Q36A4DA Installation Instructions Manual

11eer q-tectm q**a4d series packaged air conditioner
Hide thumbs Also See for Q36A4DA:
Table of Contents

Advertisement

Rated Volts
Model
& Phase
Q36A4DA0Z
-A05
230/208-1
-A10
Q36A4DB0Z
-B06
230/208-3
-B09
-B15
Q36A4DC0Z
-C06
460-3
-C09
-C15
Q42A4DA0Z
-A05
230/208-1
-A10
Q42A4DB0Z
-B06
230/208-3
-B09
-B15
Q42A4DC0Z
-C06
460-3
-C09
-C15
Q48A4DA0Z
-A05
230/208-1
-A10
Q48A4DB0Z
-B06
230/208-3
-B09
-B15
Q48A4DC0Z
-C06
460-3
-C09
-C15
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National
Electrical code (latest version), Article 310 for power conductor sizing. CAUTION: When more than one field power
circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table
310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a
raceway.
 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
 Based on 75°copper wire. All wiring must conform to the National Electrical Code and all local codes.
NOTE: The Maximum Overcurrent Protection (MOCP) value listed is the maximum value as per UL 1995
calculations for MOCP (branch-circuit conductor sizes in this chart are based on this MOCP). The actual
factory-installed overcurrent protective device (circuit breaker) in this model may be lower than the
maximum UL 1995 allowable MOCP value, but still above the UL 1995 minimum calculated value or
Minimum Circuit Ampacity (MCA) listed.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized
fuses and conductor wires in accordance with the National Electrical Code and all local codes.
TABLE 9
Electrical Specifications − Q**A4D Series
No. Field
Minimum
Power
Circuit
Circuits
Ampacity
1
26
1
31
1
57
1
20
1
23
1
32
1
50
1
11
1
12
1
16
1
25
1
31
1
31
1
57
1
24
1
24
1
32
1
51
1
11
1
12
1
16
1
25
1
33
1
33
1
57
1
25
1
25
1
33
1
51
1
12
1
12
1
16
1
25
Maximum
Field Power
External Fuse
Wire Size
or Ckt. Brkr.
40
8
40
8
60
6
25
10
25
10
35
8
50
8
15
14
15
14
20
12
25
10
50
8
50
8
60
6
35
8
35
8
35
8
60
8
15
14
15
14
20
12
25
10
40
8
40
8
60
6
30
10
30
10
40
8
60
6
15
14
15
14
20
12
30
10
Ground Wire
10
10
10
10
10
10
10
14
14
12
10
10
10
10
10
10
10
10
14
14
12
10
10
10
10
10
10
10
10
14
14
12
10
Manual 2100-752B
Page
37 of 49