Table 5 Cooling Pressure Table - Bard K36A2-A Installation Instructions Manual

Wall-mounted packaged
Table of Contents

Advertisement

Return Air
Model
Temperature °C
27° DB
19° WB
K36*2
27° DB
19° WB
27° DB
19° WB
K42*2
27° DB
19° WB
27° DB
19° WB
K48*2
27° DB
19° WB
27° DB
19° WB
K60*2
27° DB
19° WB
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating
charge being in the system, the charge should be removed and the system evacuated and recharged to serial plate
charge weight.
NOTE:
Pressure table based on high speed condenser fan operation. If condensing pressures appear
elevated, check condenser fan wiring. See "Condenser Fan Operation" (page 17).
Manual 2100-628
Page
22 of 24
TABLE 5
COOLING PRESSURE TABLE
OUTDOOR AMBIENT TEMPERATURE °C
Pressure
35
37
39
143
145
147
Low Side
High Side
368
388
408
143
145
147
Low Side
High Side
368
389
409
Low Side
High Side
Low Side
High Side
149
149
149
Low Side
High Side
377
396
415
151
152
152
Low Side
High Side
378
397
416
Low Side
High Side
Low Side
High Side
41
43
45
47
49
148
150
152
154
156
429
449
470
489
509
149
151
153
155
158
430
451
472
492
511
149
149
149
150
153
435
454
473
494
517
153
154
154
156
159
436
455
474
495
519
51
53
55
158
160
162
528
547
566
160
162
164
530
549
568
156
159
162
539
562
585
162
165
168
542
565
589