Pressure Table; Optional Field Installed Accessories; Table 9 Pressure Table - Cooling; Table 10 Optional Accessories - Bard W12AAA Installation Instructions Manual

Wall mounted package air conditioners
Table of Contents

Advertisement

COOLING
Return Air
Model
Temperature
75 deg. DB
62 deg. WB
W12AAAA
80 deg. DB
W12AAAK
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
W12AAAD
67 deg. WB
85 deg. DB
72 deg. WB
Low Side Pressure +4 PSIG
High Side Pressure +10 PSIG
Model
BOP-1A
BFAD-1
JIFM-1A
CMA-28
CRVS-1A
TABLE 9

PRESSURE TABLE

Pressure
75°
80°
Low Side
125
129
High Side
296
316
Low Side
134
138
High Side
304
324
Low Side
139
143
High Side
315
335
Low Side
125
129
High Side
314
334
Low Side
134
138
High Side
322
343
Low Side
139
143
High Side
333
355
TABLE 10

OPTIONAL FIELD INSTALLED ACCESSORIES

Description
Blank Off Plate
Barometric Fresh Air Damper
Economizer with Exhaust
Low Ambient Control
Commercial Ventilator - Spring Return
Air Temperature Entering Outdoor Coil °F
85°
90°
95°
100°
132
134
137
139
336
359
381
405
141
143
146
149
345
368
391
415
146
148
151
154
357
381
405
430
132
134
137
139
357
380
404
429
141
143
146
149
366
390
414
440
146
148
151
154
379
404
428
455
105°
100°
115°
120°
141
144
146
148
429
454
481
508
151
154
156
158
440
466
493
521
156
159
161
164
455
482
510
539
141
144
146
148
454
482
510
538
151
154
156
158
466
494
523
552
156
159
161
164
482
511
541
571
X
X
X
X
X
Manual
2100-618
Page
21 of 21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

W12aaaaW12aaadW12aaak

Table of Contents