Table 9C - - High- -Static Drive Data, 60 Hz — English
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
1
Change per
/
Turn of
2
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 1200 rpm.
Table 9D- - Standard Drive Data, 60 Hz — SI
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
1
Change per
/
Turn of
2
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (mm)
Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
524J*25A
524J*28A
524J*25H
4.3--- 5.3
4.3--- 5.3
3.0
3.0
7.4
8.6
7
15
1
/
1
/
16
16
2—B
2—B
36.8
378
1118
1024
1014--- 1200Ă
873--- 1075
1200
1100
19.4
16.7
6
6
8.16--- 10.02
6.67--- 9.43
524J*25A
524J*28A
524J*25H
94.0--- 119.4
109.2--- 134.6
3.0
3.0
239
279
36.5
49.2
2—B
2—B
(2) 1987
1062
(2) 1113
12.9
12.5
11.3--- 14.4
11.4--- 14.0
20.0
18.3
0.255
0.218
6
6
232--- 279
169--- 240
26
524J*30A
4.3--- 5.3
3.0
8.6
15
1
/
16
2—B
37.8
1024
873--- 1075
1100
16.7
6
6.67--- 9.43
524J*30A
109.2--- 134.6
3.0
279
49.2
2—B
(2) 1987
(2) 1113
12.5
11.2--- 13.9
18.3
0.218
6
169--- 240

Advertisement