Bryant DELUXE 11 SEER R-410A User Manual

Bryant DELUXE 11 SEER R-410A User Manual

Deluxe 11 seer air conditioner with puron

Advertisement

DELUXE 11 SEER
AIR CONDITIONER
WITH PURON
Bryant's Quantum Plus 591B with Puron® provides features
which cannot be matched by any other family of equipment. The
591B is a Quantum Plus air conditioning system utilizing Bry-
ant's unique Puron refrigerant. The environmentally sound
refrigerant allows you to make a responsible decision in the pro-
tection of the earth's ozone layer. Bryant's Quantum Plus sys-
®
tems meet the Energy Star
guidelines for energy efficiency.

AVAILABLE OPTIONS

Puron® Environmentally Sound Refrigerant —Is Bryant's
unique refrigerant designed to help protect the environment.
Puron is an HFC refrigerant which does not contain chlorine that
can harm the ozone layer. The most important advantage of
Puron refrigerant is that it has not been banned in future air con-
ditioning systems as the traditional refrigerant R-22 has been.
Puron refrigerant is in service in thousands of systems proving
highly reliable, environmentally sound performance.
Heavy Duty Inlet Grille —The DuraGuard™ coil protector,
made of a coated steel wire grid with vertical 3/8 in. spacing, is
designed to help protect the coil from inclement weather, van-
dalism, and incidental damage. It provides protection while not
restricting airflow and maintaining ease of coil inspection and
cleaning.
High Efficiency Performance —Is delivered through a combina-
tion of features including Bryant's Puron refrigerant, unique scroll
compressor, and advanced heat transfer surfaces. Efficiency rat-
ings are 11 to 12.5 SEER (Seasonal Energy Efficiency Ratio).
Sophisticated heat transfer surfaces utilized in Bryant's 591B
design allow heat to easily be transferred to the outdoor air and
require less energy. The unique scroll compressor found in the
591B design performs quietly and adds to the overall efficiency of
the system. Finally, Bryant's unique Puron refrigerant operates
more efficiently than ordinary R-22 refrigerant found in other sys-
tems. The efficiency levels provided by the 591B provide end
users with lower costs of operation than traditional air condition-
ing systems.
Assured Future Service —By utilizing the environmentally
sound refrigerant, Puron®, 591B models will remain serviceable
®
(R-410A)
well into the future. The Clean Air Act of 1990 has placed a cap
on production of most other refrigerants which has scheduled
reductions beginning in 2004. The resulting cap in production
ultimately results in a complete ban on many other refrigerants
in new equipment by the year 2010. These changes, required by
federal law, mean the supply of other refrigerants may be limited
in the near future making Puron the correct choice when consid-
ering long term serviceability.
Highly Reliable Performance —Is delivered through the supe-
rior design of the system and componentry. The reliability of
the existing Quantum Plus models has been proven to provide
the lowest incidence of warranty service of any product in the
Bryant family in the past few years of service. Long term reli-
ability is assured through the use of both high and low pres-
sure switches which will not allow the system to operate in the
event of a significant change in operating pressure. In doing
this, the system is protected from damage if an unusual condi-
tion arises. Finally, Bryant includes a special liquid line filter
drier designed to trap moisture and contaminants which could
otherwise shorten the life of the system.
Application Versatility —Bryant's systems utilizing Puron
refrigerant have the same application guidelines as other sys-
tems. Applications which include long line sets (50 to 175 ft) or
applications which require the system to operate at low outdoor
temperatures (below 55°F) are approved under Bryant's stan-
dard guidelines.
Bryant Coils and Fan Coils to Complete the System —Bryant
specially designs both the outdoor product and indoor coil prod-
ucts to operate with assured reliability and performance. A wide
range of indoor coil options are listed in the ratings section of
this publication.
Special Protective Devices —High and low pressure switches
and internal protection in the compressor including temperature
and current sensing overloads prevent operation under poten-
tially damaging circumstances. A special liquid line filter drier
designed to trap nearly 4 times the volume of contaminants of
standard driers provides superior protection from moisture
trapped in the system.
Electrical Range —208/230v, single phase.
Wide Range of Sizes —Available in seven sizes; 1-1/2, 2, 2-1/2,
3, 3-1/2, 4, and 5 tons.
Reliant Cabinet —Galvanized steel is coated with powder paint
to provide a superior, long lasting appearance.
Totally Enclosed Fan Motor —Protected from adverse weather
conditions.
Unit Design —Enhanced copper and aluminum heat transfer
surfaces with vertical air discharge to direct air up and away
from the area.
External Service Valves —Both service valves are back seating
type valves which are externally located. These unique valves
allow service technicians to evacuate or charge the system in
less time than standard service valves.
Easy Serviceability —One panel provides access to electrical
controls and compressor. Removal of wire dome gives access
to fan motor and removal of the top gives access to the coil.
Agency Approvals —591B models are listed with UL, c-UL,
ARI, CEC, and CSA-EEV. Special endorsements have also
been awarded these products by Energy Star® which recog-
nizes energy efficient products.
Limited Warranty —A standard five year warranty on parts with a
10 year limited warranty on the compressor. Optional warranties
are available through your Bryant distributor.
591B (60 Hz)
Sizes 018 thru 060
Form No. PDS 591B.18.1

Advertisement

Table of Contents
loading

Summary of Contents for Bryant DELUXE 11 SEER R-410A

  • Page 1 Quantum Plus models has been proven to provide the lowest incidence of warranty service of any product in the Bryant family in the past few years of service. Long term reli- ability is assured through the use of both high and low pres- sure switches which will not allow the system to operate in the event of a significant change in operating pressure.
  • Page 2 AIR IN AIR DISCHARGE AIR IN AIR DISCHARGE AIR IN NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS 55°F, (UNLESS LOW AMBIENT CONTROL IS USED) MAX.
  • Page 3 REQUIRED SUBCOOLING (°F) 018-A 024-A 030-A 036-A 042-A 048-A 060-A ® As an ENERGY STAR partner, Bryant Heating & Cooling Systems has determined that this prod- uct meets the ENERGY ® STAR guidelines for energy efficiency. —3— Vapor Tube Diameter (In.)
  • Page 4: Specifications

    UNIT SIZE-SERIES Operating Weight (Lb) ELECTRICAL Unit Volts—Hertz—Phase Operating Voltage Range* Compressor— Rated Load Amps Locked Rotor Amps Condenser Fan Motor—Full Load Amps Min Unit Ampacity for Wire Sizing Min Wire Size (60°C Copper) AWG† Min Wire Size (75°C Copper) AWG† Max Wire Length (Ft) (60°C Copper)‡...
  • Page 5 UNIT SIZE-SERIES Operating Weight (Lb) ELECTRICAL Unit Volts—Hertz—Phase Operating Voltage Range* Compressor—Rated Load Amps Locked Rotor Amps Condenser Fan Motor—Full Load Amps Min Unit Ampacity for Wire Sizing Min Wire Size (60°C Copper) AWG† Min Wire Size (75°C Copper) AWG† Max Wire Length (Ft) (60°C Copper)‡...
  • Page 6 SUGGESTED USE: All units where Winter Start Control has been added. 8. Filter Drier (Suction Line) A device for removing contaminants from refrigerant circulating in an air conditioner: 1-direction flow. See Application Guideline and Service Manual for proper application. SUGGESTED USE: All split-system air conditioners.
  • Page 7 13. Piston Body This piston body is to be used as a replacement for the FK4C Fan Coil R-22 thermostatic expansion valve when used with Puron® (R-410A) air conditioner units. Use piston and piston ring shipped with outdoor unit for installations under 50 ft.
  • Page 8 11.5 23,400 11.5 23,800 11.5 23,400 11.5 23,800 11.5 COILS + 355MAV042080 VARIABLE SPEED FURNACE 23,400 11.5 23,800 11.5 —8— SEER Bryant Gas Furnace or Accessory Accessory TDR† Puron TXV 11.0 11.0 9.95 11.0 11.0 9.75 11.0 11.0 9.95 11.0 11.0...
  • Page 9: Combination Ratings Continued

    COILS + 355MAV060100 VARIABLE SPEED FURNACE 28,600 28,000 28,600 28,000 28,600 COILS + 355MAV060120 VARIABLE SPEED FURNACE 28,600 28,000 28,600 28,600 —9— SEER Bryant Gas Furnace or Standard Accessory Accessory Rating TDR† Puron TXV 11.5 — 11.5 11.5 — 11.5 11.5...
  • Page 10 35,200 35,000 35,400 35,000 35,000 COILS + 355MAV042080 VARIABLE SPEED FURNACE 35,400 35,000 34,800 35,200 35,400 35,400 35,400 35,000 —10— SEER Bryant Gas Furnace or Standard Accessory Accessory Rating TDR† Puron TXV 10.5 11.0 11.0 10.5 11.0 11.0 10.5 11.0 11.0...
  • Page 11 COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE 40,000 40,500 40,000 40,500 40,000 40,000 40,500 COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE 40,000 40,500 —11— SEER Bryant Gas Furnace or Standard Accessory Accessory Rating TDR† Puron TXV 11.5 — 11.5 11.5 — 11.5 11.5...
  • Page 12 COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE 46,000 46,000 46,000 47,000 46,000 46,000 46,000 COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE 46,500 46,000 47,000 46,000 —12— SEER Bryant Gas Furnace or Standard Accessory Accessory Rating TDR† Puron TXV 11.5 — 11.5 11.5 — 11.5 11.5 —...
  • Page 13 58,000 59,000 58,500 58,500 58,500 59,000 COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE 56,000 58,000 59,000 58,500 58,500 58,500 59,000 —13— SEER Bryant Gas Furnace or Standard Accessory Accessory Rating TDR† Puron TXV 11.5 — 11.5 11.5 — 11.5 11.5 —...
  • Page 14 † In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause degradation in performance. Use either the accessory Time-Delay Relay KAATD0101TDR or a furnace equipped with TDR. Most Bryant furnaces are equipped with TDR.
  • Page 15 EVAP Capacity Capacity Total MBtuh† MBtuh† Total Sens‡ Kw** Total Sens‡ 591BN018-A Outdoor Section With CC5A/CD5AA024 Indoor Section 19.72 10.53 1.36 19.33 10.38 18.66 12.85 1.34 17.95 12.62 17.08 15.20 1.32 16.15 14.80 16.12 16.12 1.32 15.46 15.46 19.97 10.72 1.40 19.58 10.64 18.98 13.38...
  • Page 16 EVAP Capacity Capacity Total MBtuh† MBtuh† Total Sens‡ Kw** Total Sens‡ 591BN024-A Outdoor Section With CC5A/CD5AA030 Indoor Section 28.41 14.57 2.00 27.22 14.15 26.03 17.80 1.96 24.66 17.24 23.22 20.72 1.95 21.95 20.11 22.00 22.00 1.93 21.06 21.06 28.88 15.11 2.04 27.73 14.74 26.67 18.87...
  • Page 17 DETAILED COOLING CAPACITIES* Continued EVAP Capacity Capacity Total MBtuh† MBtuh† Total Sens‡ Kw** Total Sens‡ 591BN030-A Outdoor Section With CC5A/CD5AA036 Indoor Section 34.62 17.93 2.44 33.18 17.42 31.79 22.11 2.40 30.14 21.45 28.42 25.88 2.38 26.87 25.12 27.16 27.16 2.36 26.00 26.00 35.12 18.58 2.50...
  • Page 18 DETAILED COOLING CAPACITIES* Continued EVAP Capacity Capacity Total MBtuh† MBtuh† Total Sens‡ Kw** Total Sens‡ 591BN036-A Outdoor Section With CC5A/CD5AA042 Indoor Section 42.30 21.87 2.99 40.41 21.15 38.65 26.76 2.96 36.69 25.95 1050 34.55 31.25 2.93 32.77 30.37 32.91 32.91 2.91 31.49 31.49 42.98 22.71...
  • Page 19 DETAILED COOLING CAPACITIES* Continued EVAP Capacity Capacity Total MBtuh† MBtuh† Total Sens‡ Kw** Total Sens‡ 591BN036-A Outdoor Section With CC5A/CD5AA042 Indoor Section 42.30 21.87 2.99 40.41 21.15 38.65 26.76 2.96 36.69 25.95 1050 34.55 31.25 2.93 32.77 30.37 32.91 32.91 2.91 31.49 31.49 42.98 22.71...
  • Page 20 DETAILED COOLING CAPACITIES* Continued EVAP Capacity Capacity Total MBtuh† MBtuh† Total Sens‡ Kw** Total Sens‡ 591BN042-A Outdoor Section With CC5A/CD5AA048 Indoor Section 47.78 25.26 3.42 46.00 24.38 44.33 30.45 3.39 42.28 29.55 1225 40.04 35.47 3.36 38.02 34.48 37.66 37.66 3.32 36.11 36.11 48.46 26.11...
  • Page 21 DETAILED COOLING CAPACITIES* Continued EVAP Capacity Capacity Total MBtuh† MBtuh† Total Sens‡ Kw** Total Sens‡ 591BN048-A Outdoor Section With CC5A/CD5AA060 Indoor Section 54.78 28.94 3.91 52.62 27.99 50.84 34.84 3.89 48.53 33.83 1400 46.15 40.77 3.87 43.72 39.57 43.27 43.27 3.84 41.47 41.47 55.80 30.03...
  • Page 22 DETAILED COOLING CAPACITIES* Continued EVAP Capacity Capacity Total MBtuh† MBtuh† Total Sens‡ Kw** Total Sens‡ 591BN060-A Outdoor Section With CC5A/CD5AW060 Indoor Section 69.22 36.58 4.95 66.19 35.29 64.38 44.16 4.89 61.20 42.74 1750 58.36 51.45 4.84 55.10 49.85 54.62 54.62 4.77 52.25 52.25 70.41 38.02...
  • Page 23 °F 15.90 73.70 0.77 17.50 75.30 0.79 19.20 76.80 0.80 21.10 78.40 0.82 23.00 80.20 0.84 25.10 82.00 0.87 22.10 76.10 1.29 24.40 77.80 1.31 26.70 79.50 1.33 29.20 81.30 1.36 31.90 83.20 1.38 34.60 85.10 1.41 26.30 77.10 1.58 28.90 78.80 1.60...
  • Page 24 CONDENSER ONLY RATINGS* Continued °F 32.70 77.00 1.99 36.00 78.70 2.01 39.50 80.60 2.04 43.20 82.50 2.07 47.10 84.50 2.10 51.20 86.50 2.14 39.20 78.20 2.25 43.10 80.10 2.28 47.20 82.00 2.31 51.60 84.00 2.36 56.30 86.20 2.40 61.10 88.40 2.45 45.50 80.40...
  • Page 25 CONDENSER ONLY RATINGS* Continued 58.20 83.60 3.22 63.90 85.80 3.30 69.80 88.20 3.38 76.10 90.60 3.47 82.60 93.20 3.57 89.40 95.80 3.67 * ARI listing applies only to systems shown in Ratings and Performance table. kW — Total Power (Kw) SDT —...
  • Page 26 MATCHED SYSTEM A98599 —26—...
  • Page 27 —27—...
  • Page 28: Guide Specifications

    Fans Condenser fan will be direct-drive propeller type, discharging air upward. © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St. Fans Condenser fan will be direct-drive propeller type, discharging air upward.

This manual is also suitable for:

591b