Bryant 524J Installation, Start-Up And Service Instructions Manual page 16

Packaged air-handling units, 60 hz with puron (r-410a) refrigerant
Table of Contents

Advertisement

UNIT
V ---PH ---Hz
208/230--- 3--- 60
524J*25A
460--- 3--- 60
524J*25H
575--- 3--- 60
208/230--- 3--- 60
460--- 3--- 60
524J*28A
575--- 3--- 60
208/230--- 3--- 60
460--- 3--- 60
524J*30A
575--- 3--- 60
See Legend and Notes below.
UNIT
V ---PH ---Hz*
208/230--- 3--- 60
524J*25A
460--- 3--- 60
524J*25H
575--- 3--- 60
208/230--- 3--- 60
524J*28A
460--- 3--- 60
524J*30A
575--- 3--- 60
See Legend and Notes below.
Legend and Notes for Tables 4 and 5
LEGEND:
FLA
--- Full Load Amps
MOCP
--- Maximum Overcurrent Protection
{ Motors are designed for satisfactory operation within 10% of
normal voltage shown. Voltages should not exceed the limits
shown in the Voltage Limits column.
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calcu-
lated in accordance with The NEC. Article 440.
2. Motor FLA values are established in accordance with Under-
writers' Laboratories (UL). Standard 1995.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the formula in the example
(see column to the right) to determine the percentage of volt-
age imbalance.
4. Installation with Accessory Electric Heaters
Size the Field Power Wiring between the heater TB1 and the
524J indoor fan motor per NEC Article 430--- 28 (1) or (2)
(depends on length of conduit between heater enclosure and
524J power entry location). Install wires in field --- installed
conduit.
Table 4 – Electrical Data, Standard Motors
VOLTAGE
{
LIMITS
187--- 253
414--- 506
518--- 632
187--- 253
414--- 506
518--- 632
187--- 253
414--- 506
518--- 632
Table 5 – Electrical Data, Alternate Motors
VOLTAGE
LIMITS
187--- 253
414--- 506
518--- 632
187--- 253
414--- 506
518--- 632
FAN MOTOR
Hp (kW)
FLA
5.0 (3.73)
14.7/13.6
5.0 (3.73)
6.8
5.0 (3.73)
5.1
7.5 (5.59)
21.4/19.4
7.5 (5.59)
9.7
7.5 (5.59)
7.8
10.0 (7.46)
28.0/25.2
10.0 (7.46)
12.6
10.0 (7.46)
10.3
FAN MOTOR
Hp (kW)
FLA
7.5 (5.59)
21.4/19.4
7.5 (5.59)
9.7
7.5 (5.59)
7.8
10.0 (7.46)
28.0/25.2
10.0 (7.46)
12.6
10.0 (7.46)
10.3
Example: Supply voltage is 230-3-60
% Voltage Imbalance
= 100 x
AB = 393 v
BC = 403 v
AC = 396 v
(393 + 403 + 396)
Average Voltage =
3
=
397
Determine maximum deviation from average voltage.
(AB) 397 – 393 = 4 v
(BC) 403 – 397 = 6 v
(AC) 397 – 396 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
= 1.5%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
16
POWER SUPPLY
Minimum
MOCP
Circuit Amps
18.4/17.0
30/25
8.5
15
6.4
15
26.9/24.3
45/40
12.1
20
9.8
15
35.0/31.5
60/50
15.8
25
12.9
20
POWER SUPPLY
Minimum
MOCP
Circuit Amps
26.9/24.3
45/40
12.1
20
9.8
15
35.0/31.5
60/50
15.8
25
12.9
20
max voltage deviation from average voltage
average voltage
1192
=
3
6
397

Advertisement

Table of Contents
loading

This manual is also suitable for:

524j25a524j28a524j30a524j series

Table of Contents