Fan Motor Lubrication; Fan Shaft Bearings; Centering Fan Wheel; Fan Shaft Position Adjustment - Bryant 524J Installation, Start-Up And Service Instructions Manual

Packaged air-handling units, 60 hz with puron (r-410a) refrigerant
Table of Contents

Advertisement

Fan Motor Lubrication - - Fan motor supplied with unit is
permanently
lubricated
lubrication.
Fan Shaft Bearings - - Size 25- - 30 units have pillow- - block
bearings (Fig. 22) that must be lubricated with suitable
bearing grease approximately every 3 months. See Table 7
for suitable lubricants.
Table 7 – Lubricant Data
MANUFACTURER
Mobil
Sunoco
Texaco
Texaco
*Preferred lubricant, contains rust and oxidation inhibitors.
Fig. 22 - - Fan Shaft, Bearings, and Fan Wheel (Typical)
and
requires
no
further
LUBRICANT
Mobilplex EP No. 2
Prestige 42
Multifak 2
Regal AFB--- 2*
C10698
Fig. 24 - - Fan Motor Mounting
Centering Fan Wheel - - If fan and fan shaft assembly are
not properly centered, blades may scrape against the
blower side scroll plate or may create an objectionable
whistling noise. It may be necessary to adjust individual
fan wheels or move entire fan shaft. See the following two
sections.
Fan Shaft Position Adjustment - - Loosen setscrew or
locking collar of each fan shaft bearing. Slide shaft into
correct position and replace locking collar (Fig. 23). To
replace locking collar, push collar up against inner face of
bearing. Turn collar in direction of fan rotation until tight,
and tighten setscrew. Tightening locking collar in
direction of fan rotation results in further tightening of
collar should setscrew work itself loose.
Fig. 23 - - Fan Shaft Bearing
20
C10699
C10700

Advertisement

Table of Contents
loading

This manual is also suitable for:

524j25a524j28a524j30a524j series