Bryant 524J Installation, Start-Up And Service Instructions Manual

Bryant 524J Installation, Start-Up And Service Instructions Manual

Packaged air-handling units, 60 hz with puron (r-410a) refrigerant

Advertisement

Quick Links

524J
PACKAGED AIR- - HANDLING UNITS, 60 Hz
R
WITH PURON
(R- - 410A) REFRIGERANT
SIZES 25, 28, 30
TABLE OF CONTENTS
SAFETY CONSIDERATIONS
PRE- - INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . .
Moving and Storage
. . . . . . . . . . . . . . . . . . . . . . . . . .
Rigging
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . .
General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Uncrating
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Positioning
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Isolation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Piping Access
Refrigerant Piping
. . . . . . . . . . . . . . . . . . . . . . . . . .
Condensate Drain
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan Motors and Drives
. . . . . . . . . . . . . . . . . . . . . . .
Power Supply and Wiring
Connecting Ductwork
. . . . . . . . . . . . . . . . . . . . . . .
Return- - Air Filters
. . . . . . . . . . . . . . . . . . . . . . . . . .
START- - UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Panels
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan Motor Lubrication
. . . . . . . . . . . . . . . . . . . . . . .
Fan Shaft Bearings
. . . . . . . . . . . . . . . . . . . . . . . . . .
Centering Fan Wheel
. . . . . . . . . . . . . . . . . . . . . . . .
Fan Shaft Position Adjustment
Individual Fan Wheel Adjustment
Fan Belts
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan Rotation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan Pulley Alignment
. . . . . . . . . . . . . . . . . . . . . . .
Pulley and Drive Adjustment
Condensate Drains
. . . . . . . . . . . . . . . . . . . . . . . . . .
Return- - Air Filters
. . . . . . . . . . . . . . . . . . . . . . . . . .
Installation, Start- -Up
and Service Instructions
. . . . . . . . . . . . . . . . . . .
2–18
11
. . . . . . . . . . . . . . . . . . . .
11
11
14
15
. . . . . . . . . . . . . . . . . . . .
15
17
17
19
19–32
19
20
20
20
. . . . . . . . . . . . . . . .
20
. . . . . . . . . . . . . .
21
21
21
21
. . . . . . . . . . . . . . . . . .
21
21
21
Coil Removal
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cleaning Cooling Coil
1
Cleaning Insulation
2
Replacing Filters
2
START- - UP CHECKLIST
2
SAFETY CONSIDERATIONS
2
Improper installation, adjustment, alteration, service,
2
maintenance, or use can cause explosion, fire, electrical
2
shock or other conditions which may cause personal
injury or property damage. Consult a qualified installer,
9
service agency, or your distributor or branch for
information or assistance. The qualified installer or
agency must use factory- - authorized kits or accessories
when modifying this product. Refer to the individual
instructions package
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloths for brazing operations and
have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and appropriate
national electrical codes (in USA, ANSI/NFPA70,
National Electrical Code (NEC); in Canada, CSA C22.1)
for special requirements.
It is important to recognize safety information. This is the
safety- - alert symbol
unit and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety- - alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or
death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify
unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. When you see this symbol on the
22
22
22
22
35- - 36

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 524J

  • Page 1 524J PACKAGED AIR- - HANDLING UNITS, 60 Hz WITH PURON (R- - 410A) REFRIGERANT SIZES 25, 28, 30 Installation, Start- -Up and Service Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS ....
  • Page 2: Pre- - Installation

    Do not remove plastic wrap or skid from unit until final installation. Rigging - - All 524J Series units can be rigged by using the shipping skid. Units are shipped fully assembled. Do not remove shipping skids or protective covering until unit is ready for final placement;...
  • Page 3 Table 1A — 524J***A Physical Data, English — Cooling Units UNIT 524J* NOMINAL CAPACITY (Tons) OPERATING WEIGHT (lb) Base Unit with TXV Plenum FANS Qty...Diam. (in.) Nominal Airflow (cfm) Airflow Range (cfm) Nominal Motor Hp (Standard Motor) 208/230---3---60 and 460---3---60...
  • Page 4 Table 1B —524J***A Physical Data, SI — Cooling Units UNIT 524J* NOMINAL CAPACITY (kW) OPERATING WEIGHT (kg) Base Unit with TXV Plenum FANS Qty...Diam. (mm) Nominal Airflow (L/s) Airflow Range (L/s) Nominal Motor kW (Standard Motor) 208/230---3---60 and 460---3---60 575---3---60...
  • Page 5 Table 1C — 524J*25H Physical Data, English — Heat Pump Units UNIT 524J* NOMINAL CAPACITY (Tons) OPERATING WEIGHT (lb) Base Unit with TXV Plenum FANS Qty...Diam. (in.) Nominal Airflow (cfm) Airflow Range (cfm) Nominal Motor Hp (Standard Motor) 208/230---3---60 and 460---3---60...
  • Page 6 Table 1D — 524J*25H Physical Data, SI — Heat Pump Units UNIT 524J* NOMINAL CAPACITY (kW) OPERATING WEIGHT (kg) Base Unit with TXV Plenum FANS Qty...Diam. (mm) Nominal Airflow (L/s) Airflow Range (L/s) Nominal Motor kW (Standard Motor) 208/230---3---60 and 460---3---60...
  • Page 7 4. Liquid piping not supplied by Carrier. 5. Duct flange is factory supplied and field installed. Fig. 1 - - Dimensions – Size 25 LEGEND Direction of airflow. with electric heat accessory) UNIT WEIGHT UNIT lb (kg) 524J*25A 730 (331) 524J*25H 720 (326) C10834...
  • Page 8 • Local codes or jurisdiction may prevail. 4. Liquid piping not supplied by Carrier. 5. Duct flange is factory supplied and field installed. 6. 40RUS may require alternate or additional field favricated poping access holes UNIT lb (kg) 524J*28A 1050 (477) 524J*30A 1062 (482) C10835...
  • Page 9: Unit Positioning

    5 2 4 J E 2 5 A 0 0 0 A 2 0 A A A _____________ Model Type 524J = Bryant Fan Coil Puronr R--- 410A Refrigerant Voltage E = 460/3/60 P = 208/ 230/3/60 T = 575/3/60...
  • Page 10 Typical positioning and alternate return air locations are shown in Fig. 6. Alternate return air locations can be used by moving the unit panel from the alternate return air location to the standard return air location. Refer to overhead suspension accessory drawing (Fig. 7) for OVERHEAD SUSPENSION ACCESSORY —...
  • Page 11: Unit Isolation

    R- - 410A. See Table 2 for part numbers. Knockouts are provided in the unit corner posts for 524J refrigerant piping. See Fig. 8, which also lists recommended knockouts and access holes to use for each 524J unit size.
  • Page 12 Fig. 9 - - Face- - Split Coil Suction and Liquid Line Piping (Typical) FIRST ON/LAST OFF = B VERTICAL INSTALLATION FIRST ON/LAST OF F = A HORIZONTAL INSTALLATIO N Fig. 10 - - Typical Evaporator Coil Connections (524J) EQUALIZER LINE SENSING BULB 15 DIAMS...
  • Page 13 Table 2 – Factory- - Installed Nozzle and Distributor Data COIL TYPE UNIT 524J*25A 4 Row 524J*28A 4 Row 524J*30A 4 Row 524J*25H 4 Row Feeder tube size is in. (6.35 mm). NOTE: Hot gas bypass applications require field---supplied auxiliary side connector.
  • Page 14: Condensate Drain

    UNIT ACCESS HOLE NO. 524J*30A See Fig. 8 for access hole location by number. † Fittings are listed in order from header or tee stub connection out to access hole in corner support post. Condensate Drain - - Install a trapped condensate drain line to unit connection as shown in Fig.
  • Page 15: Fan Motors And Drives

    1 — fan motor 1 — adjustable motor pulley 1 — fan pulley 2 — matched fan belts (524J*25A- - 30A units) For instructions on changing fan rotation, changing drive speeds and adjusting drives, see Pulley and Drive Adjustment in the Service section.
  • Page 16 4. Installation with Accessory Electric Heaters Size the Field Power Wiring between the heater TB1 and the 524J indoor fan motor per NEC Article 430--- 28 (1) or (2) (depends on length of conduit between heater enclosure and 524J power entry location). Install wires in field --- installed conduit.
  • Page 17: Connecting Ductwork

    Table 6 – Fan Contactor Coil Data UNIT VOLTAGE 524J* (vac) 25A, 25H, 28A, 30A Connecting Ductwork - - Refer to the System Design Manual for the recommended design and layout of ductwork. Fig. 18 shows recommended duct connection to units with 2 fans.
  • Page 18 C10696 Fig. 18 - - Typical Fan Discharge Connections for Multiple Fan Units C10697 Fig. 19 - - Duct Flange Installation...
  • Page 19: Start- - Up

    START- -UP Before starting unit, check the following and correct as necessary: S Is unit solidly supported? S Is fan adjusted for speed and pulley alignment? S Are pulleys, motor, and bearings securely mounted? S Are there any loose parts that will rattle or vibrate? S Is condensate drain pan pitched for correct drainage? S Are coil baffle plates tight against coil to prevent air bypass?
  • Page 20: Fan Motor Lubrication

    Fan Motor Lubrication - - Fan motor supplied with unit is permanently lubricated requires lubrication. Fan Shaft Bearings - - Size 25- - 30 units have pillow- - block bearings (Fig. 22) that must be lubricated with suitable bearing grease approximately every 3 months. See Table 7 for suitable lubricants.
  • Page 21: Individual Fan Wheel Adjustment

    Individual Fan Wheel Adjustment - - Loosen the 2 locking bolts holding fan wheel hub to shaft. See Fig. 22. Position fan wheel in center of the fan housing and tighten locking bolts. Clearance between wheel and housing should be the same on both sides. Fan Belts - - Motor mounting plate and motor support angles are slotted to permit both vertical and horizontal adjustment.
  • Page 22: Coil Removal

    Coil Removal - - Remove unit panels and corner posts as required. Disconnect coil connections and remove fastening screws. Remove coil through end or side sections of unit. Cleaning Cooling Coil - - Remove return- - air filters. Remove any heavy dirt that may have accumulated on underside of coil.
  • Page 23 Table 8A - - Fan Motor Data, Standard Motor — English 524J*25A UNIT 524J*25H 208/230---3---60 and 460---3---60 Speed (rpm) 1745 Frame (NEMA) S184T Shaft Dia (in.) 575---3---60 Speed (rpm) 1745 Frame (NEMA) 184T Shaft Dia (in.) LEGEND NEMA — National Electrical Manufacturers Association Table 8B - - Fan Motor Data, Alternate Motor —...
  • Page 24 Table 8C - - Fan Motor Data, Standard Motor — SI 524J*25A UNIT 524J*25H 208/230---3---60 and 460---3---60 Speed (r/s) 29.08 Shaft kW 3.73 Frame (NEMA) S184T Shaft Dia (mm) 28.6 575---3---60 Speed (r/s) 29.08 Shaft kW 3.73 Frame (NEMA) 184T Shaft Dia (mm) 28.6...
  • Page 25 Moveable Motor Pulley Flange MAX FULL TURNS FROM CLOSED POSITION SHAFTS CENTER DISTANCE (in.) † Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting. 524J*25A 524J*28A 524J*30A 524J*25H 3.7--- 4.7 4.3--- 5.3 4.3--- 5.3 11.0...
  • Page 26 Moveable Motor Pulley Flange MAX FULL TURNS FROM CLOSED POSITION SHAFTS CENTER DISTANCE (mm) † Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting. 524J*25A 524J*28A 524J*30A 524J*25H 4.3--- 5.3 4.3--- 5.3 4.3--- 5.3 2—B...
  • Page 27 Flange MAX FULL TURNS FROM CLOSED POSITION SHAFTS CENTER DISTANCE (mm) † It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s 524J*25A 524J*28A 524J*30A 524J*25H 109.2--- 134.6 109.2--- 134.6 109.2--- 134.6 36.5...
  • Page 28 Table 10A - - 524J Standard Fan Performance Data — AIRFLOW UNIT (Cfm) 6,000 1.25 7,000 1.93 524J*25A 8,000 2.83 524J*25H 9,000 3.97 10,000 5.38 7,500 1.29 8,750 1.98 10,000 2.88 524J*28A 11,250 4.03 12,500 5.46 15,000 8.84 9,000 1.99 10,500 3.16...
  • Page 29 Table 10B - - 524J Standard Fan Performance Data — AIRFLOW UNIT (L/s) 2830 8.86 0.94 3300 10.14 1.44 524J*25A 3780 11.43 2.11 524J*25H 4250 12.74 2.96 4720 14.05 4.01 3540 7.60 0.96 4130 8.68 1.47 4720 9.78 2.15 524J*28A 5310 10.89...
  • Page 30 Table 10C - - 524J High- -Capacity Fan Performance Data — AIRFLOW UNIT (Cfm) 6,000 1.29 7,000 1.99 524J*25A 8,000 2.92 524J*25H 9,000 4.10 10,000 5.56 7,500 1.39 8,750 2.14 10,000 3.12 524J*28A 11,250 4.37 12,500 5.92 9,000 2.18 10,500 3.37...
  • Page 31 Table 10D - - 524J High- -Capacity Fan Performance Data — AIRFLOW UNIT (L/s) 2830 9.03 0.96 3330 10.34 1.48 524J*25A 3780 11.67 2.17 524J*25H 4250 13.01 3.05 4720 14.36 4.15 3540 7.94 1.04 4130 9.08 1.59 4720 10.24 2.33...
  • Page 32 3. Refer to fan motor and drive tables for additional data. Legend and Notes for Tables 10A and 10C FACTORY-SUPPLIED PRESSURE DROP — ENGLISH UNIT 524J*25A 524J*25H 524J*28A 524J*30A Legend and Notes for Tables 10B and 10D FACTORY-SUPPLIED PRESSURE DROP — SI...
  • Page 34 2011 Bryant Heating and Cooling Systems. D 7310 W. Morris St. D Indianapolis, IN 46231 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Printed in U.S.A. Edition Date: 01/11 Catalog No: II524J---07...
  • Page 35: Outdoor Unit

    PIPING HAS FOAM SHIPPING BLOCK BEEN REMOVED FROM THE TXV (Thermostatic Expansion Valve)? (Y/N) ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR UNIT (524J***A) OR OUTDOOR UINT (524J*25H) COILS AS REQUIRED? (Y/N) HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS,...
  • Page 36 OIL LEVEL AT FULL? (Y/N) NOTES: 2011 Bryant Heating and Cooling Systems. D 7310 W. Morris St. D Indianapolis, IN 46231 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. COMP A1 ____/____/____ Printed in U.S.A.