Bryant PURON 583B User Manual

Single-package gas heating/electric cooling units

Advertisement

Quick Links

SINGLE-PACKAGE
GAS HEATING/ELECTRIC
COOLING UNITS
UNIT 583B
Single-Package Rooftop Products with Energy-Saving Features
and Puron® refrigerant.
Direct Spark Ignition
Low Sound Levels
Up to 81% AFUE
12 SEER
Variable Speed Blower Option

FEATURES/BENEFITS

One-piece heating and cooling units with low sound levels, easy
installation, low maintenance, and dependable performance.
Puron® Environmentally Sound Refrigerant is Bryant's
unique refrigerant designed to help protect the environment.
Puron is an HFC refrigerant which does not contain chlorine that
can harm the ozone layer. The most important advantage of
Puron refrigerant is that it has not been banned in future air con-
ditioning systems as the traditional refrigerant R-22 has been.
Puron refrigerant is in service in thousands of systems proving
highly reliable, environmentally sound performance.
Perfect Heat, Perfect Humidity™ featuring Variable Speed
Blower motors provides better comfort and energy efficiency.
You can expect up to 30 times better dehumidification; a SEER
boost of up to 12.7; economical constant fan for less than $30 a
year, which provides improved indoor air quality and more even
temperatures from room to room; and reduced indoor noise due
to lower air velocity. In addition, you'll realize improved installation
flexibility with 3 different airflow choices for best overall comfort.
EASY INSTALLATION—Factory-assembled package is a com-
pact, fully self-contained, combination gas heating/electric cool-
ing unit that is pre-wired, pre-piped, and pre-charged for
minimum installation expense.
These units are available in a variety of standard and optional
heating/cooling size combinations with voltage options to meet
residential and light commercial requirements. Units are light-
weight and install easily on a rooftop or at ground level. The high
tech composite basepan eliminates rust problems associated
with ground level applications.
CONVERTIBLE DUCT CONFIGURATION—Unit is designed
for easy use in either downflow or horizontal applications. Each
unit is easily converted from horizontal to downflow.
EFFICIENT OPERATION
High-efficiency design offers SEER (Seasonal Energy Effi-
ciency Ratios) of 12.0 and AFUE (Annual Fuel Utilization Effi-
ciency) ratings as high as 81%.
Energy-saving, direct spark ignition saves gas by operating
only when the room thermostat calls for heating. Standard units
are furnished with natural gas controls. A low-cost field-installed
kit for propane conversion is available for all units.
583B units with an "N" in the thirteenth position of model #
are dedicated Low NOx units designed for California installa-
tions. These models meet the California maximum oxides of ni-
trogen (NOx) emissions requirement of 40 nanograms/joule or
less as shipped from the factory and MUST be installed in Cali-
fornia Air Quality Management Districts where a Low NOx rule
exists.
DURABLE, DEPENDABLE COMPONENTS
Compressors are designed for high efficiency. Each compres-
sor is hermetically sealed against contamination to help promote
longer life and dependable operation. Each compressor also has
vibration isolation to provide quieter operation. All compressors
have internal high pressure and overcurrent protection.
Monoport inshot burners produce precise air-to-gas mixture,
which provides for clean and efficient combustion. The large
monoport on the inshot (or injection type) burners seldom, if
ever, requires cleaning. All gas furnace components are acces-
sible in one compartment.
Turbo-tubular™ heat exchangers are constructed of alumi-
nized steel for corrosion resistance and optimum heat transfer
for improved efficiency. The tubular design permits hot gases to
make multiple passes across the path of the supply air.
In addition, dimples located on the heat exchanger walls force
the hot gases to stay in close contact with the walls, improving
heat transfer.
Direct-drive multi-speed, PSC (permanent split capacitor)
blower motor is standard on all 583B models.
Direct-drive, PSC condenser-fan motors are designed to help
reduce energy consumption and provide for cooling operation
down to 40°F outdoor temperature. Motormaster® II low ambient
kit is available as a field-installed accessory.
Form No. PDS 583B.24.3
Model 583B
Sizes 024-060
2 to 5 Nominal Tons
Low NOx Models Available

Advertisement

Table of Contents
loading

Summary of Contents for Bryant PURON 583B

  • Page 1: Features/Benefits

    Blower motors provides better comfort and energy efficiency. You can expect up to 30 times better dehumidification; a SEER boost of up to 12.7; economical constant fan for less than $30 a year, which provides improved indoor air quality and more even temperatures from room to room;...
  • Page 2: Model Number Nomenclature

    Corporate thermostats include the Time Guard® II anti-short cycle protection circuitry. If a non-corporate thermostat without anti-short cycle protection is used the Time Guard II field in- stalled anti-short cycle kit is recommended. Refrigerant system is designed to provide dependability. Liquid filter dryers are used to promote clean, unrestricted operation.
  • Page 3: Table Of Contents

    10.4 ‡“A” Capacity– 80°F db/67°Fwb indoor & 95°Fdb outdoor. NOTES: 1. Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard: 80°F db, 67°F wb indoor entering-air tempera- ture and 95°F db outdoor entering-air temperature.
  • Page 4 HEATING CAPACITIES AND EFFICIENCIES HEATING INPUT UNIT 583B (Btuh) 024040 40,000 030040 024060 030060 60,000 036060 042060 90,000 036090 90,000 042090 048090 90,000 060090 90,000 048115 115,000 060115 048130 130,000 060130 LEGEND AFUE — Annual Fuel Utilization Efficiency NOTE: Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. OUTDOOR SOUND: OCTAVE BAND DATA —...
  • Page 5: Physical Data

    Quantity REFRIGERANT (R-410A) Quantity (lb) REFRIGERANT METERING DEVICE Orifice ID (in.) AccuRater® Piston CONDENSER COIL Rows—Fins/in. Face Area (sq ft) CONDENSER FAN Nominal Cfm Diameter (in.) Motor Hp (Rpm) EVAPORATOR COIL Rows—fins/in. Face Area (sq ft) EVAPORATOR BLOWER Nominal Airflow (Cfm) Size (in.)
  • Page 6: Physical Data

    Quantity REFRIGERANT (R-410A) Quantity (lb) REFRIGERANT METERING DEVICE Orifice ID (in.) AccuRater® Piston CONDENSER COIL Rows—Fins/in. Face Area (sq ft) CONDENSER FAN Nominal Cfm Diameter (in.) Motor Hp (Rpm) EVAPORATOR COIL Rows—fins/in. Face Area (sq ft) EVAPORATOR BLOWER Nominal Airflow (Cfm) Size (in.)
  • Page 7: Options And Accessories

    Factory-installed options Coil options include copper/copper and vinyl-coated construc- tion for refrigerant coils. Units are shipped standard with copper tube/aluminum fin construction. See model number nomencla- ture for coil options. Electronic Variable-Speed Motor — ICM Motors (Integrated Control Motor) provide variable-speed operation to optimize comfort levels year round.
  • Page 8 Economizer A99314 Filter Rack A99316 Manual Outside Air Damper REPLACEMENT PANEL MANUAL OUTSIDE AIR HOOD DAMPER BLADE —8— A99315 A99317...
  • Page 9: Base Unit Dimensions

    BASE UNIT DIMENSIONS — 583B024-036 REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm) Evaporator coil access side ....36 (914) Power entry side (except for NEC requirements) ..36 (914) Unit top .
  • Page 10: Base Unit Dimensions

    BASE UNIT DIMENSIONS – 583B042-060 REQUIRED CLEARANCE FOR OPERATION AND SERVICING EVAP. COIL ACCESS SIDE...36.00 [914.0] POWER ENTRY SIDE...36.00 [914.0] (EXCEPT FOR NEC REQUIREMENTS) UNIT TOP ...36.00 [914.0] SIDE OPPOSITE DUCTS ...36.00 [914.0] DUCT PANEL ...12.00 [304.8] * *MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 in. [304.8 mm.] FROM WALL THEN SYSTEM PERFORMANCE MAYBE COMPR OMISED.
  • Page 11: Accessory Dimensions

    HVAC unit base Screw (NOTE A) *Gasketing outer flange Flashing field supplied Roofing material field supplied Cant strip field supplied *Provided with roofcurb Roof Curb for Small Cabinet Note A: When unit mounting screw is used, retainer bracket must also be used. B Typ.
  • Page 12: Selection Procedure

    Downflow Discharge on page 16. For 208 v operation, REQUIRED COOLING deduct 10% from value given. At .23 ESP (external static pressure), the fan will deliver 1327 cfm at low speed. The fan speed should be set at low speed. SELECT UNIT THAT CORRESPONDS TO POWER SOURCE AVAILABLE.
  • Page 13: Performance Data

    583B024 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser 23.7 19.6 1.74 22.4 18.9 1.91 21.2 18.4 2.11 19.1 17.1 2.37 16.9 15.9 2.73 14.7 14.7 3.16 583B030 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser 29.0 25.2 2.11 27.5 24.5...
  • Page 14 583B036 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser 35.2 30.3 2.58 32.9 28.7 2.83 31.0 27.9 3.11 27.9 26.0 3.49 25.5 24.7 3.85 22.2 22.2 4.48 583B042 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser 40.9 35.2 2.93 38.8 34.2...
  • Page 15 PSC — Permanent Split Capacitor NOTES: 1. Ratings are net; they account for the effects of the evaporator-fan motor power and heat. 2. Direct interpolation is permissible. Do not extrapolate. 3. The following formulas may be used: PERFORMANCE DATA (cont)
  • Page 16 583B STANDARD UNIT—WET COIL AIR FLOW DELIVERY 230 AND 460 VOLT Motor Unit 583B Speed Watts Watts — — Watts — High — Watts Watts 1195 1134 Watts — High — Watts 1431 1398 Watts — — 1491 Watts — High —...
  • Page 17 583B COOLING DRY COIL ICM AIRFLOW—SMALL CABINET CFM ADJUST PIN SELECT UNIT SIZE EXTERNAL STATIC 0.0–0.4 PRESSURE RANGE COOLING COOLING DEHUMIDIFY COOLING COOLING DEHUMIDIFY COOLING 1025 COOLING DEHUMIDIFY 583B COOLING DRY COIL ICM AIRFLOW—LARGE CABINET CFM ADJUST PIN SELECT UNIT SIZE EXTERNAL STATIC PRESSURE RANGE...
  • Page 18 * As the height above sea level increases, there is less oxygen per cubic ft of air. Therefore, heat input rate should be reduced at higher altitudes. † Orifices available through your Bryant distributor. 583B ICM FIOP WET COIL PRESSURE DROP...
  • Page 19: Typical Piping And Wiring

    TYPICAL PIPING AND WIRING ROOF-MOUNTING CURB SUPPLY-AIR FLEXIBLE DUCT CONCENTRIC DIFFUSER BOX (FIELD-SUPPLIED) RETURN TOP COVER ROOF RETURN-AIR FLEXIBLE DUCT CEILING INDOOR THERMOSTAT FROM GAS LINE *NEC - NATIONAL ELECTRICAL CODE —19— C00023 FROM POWER SOURCE DISCONNECT PER NEC* C00022...
  • Page 20: Application Data

    Condensate trap — A 2-in. condensate trap must be field supplied. 1” MIN. Ductwork — Secure downflow discharge ductwork to roof curb. For horizontal discharge applications, attach ductwork to unit with flanges. To convert a unit to downflow discharge — Units are equipped with factory-installed inserts in the down-flow openings.
  • Page 21: Electrical Data

    2%. Use the following formula to determine the percentage of voltage imbalance. % Voltage imbalance max voltage deviation from average voltage = 100 x average voltage ELECTRICAL DATA VOLTAGE OUTDOOR FAN COMPRESSOR RANGE 13.5 61.0 14.7 73.0 63.0 15.4...
  • Page 22: Typical Wiring Schematics

    TYPICAL WIRING SCHEMATIC—208/230-1-60 SHOWN C99076 —22—...
  • Page 23 TYPICAL WIRING SCHEMATIC—208/230-3-60 SHOWN C99077 —23—...
  • Page 24 TYPICAL WIRING SCHEMATIC—460-3-60 SHOWN C99078 —24—...
  • Page 25 ICM FIOP WIRING SCHEMATIC—208/230-1-60 —25—...
  • Page 26: Controls

    The unit is in a “standby” condition, waiting for the next “call for cooling” from the room thermostat. The ICM FIOP indoor blower operation with a call for fan oper- ation (G) in cooling mode will perform by the on/off delay profile selected on the Easy Select™...
  • Page 27: Guide Specifications

    GUIDE SPECIFICATIONS as shown on equipment drawings or factory optional variable speed motor and control. 2. Fan wheel shall be made from steel, and shall be double-inlet type with forward curved blades with corrosion resistant finish. Fan wheel shall be dynamically balanced.
  • Page 28: Guide Specifications

    5. Manual Outdoor Air Damper: © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 GUIDE SPECIFICATIONS continued Package shall consist of damper, birdscreen, and rain- hood which can be preset to admit outdoor air for year- round ventilation.

Table of Contents