Indoor Air Quality
If the optional indoor air quality sensor is installed, the
RTU- - MP will maintain indoor air quality within the space
at the user configured differential setpoint. The setpoint is
the difference between the indoor air quality and an
optional outdoor air quality sensor. If the outdoor air
quality is not present then a fixed value of 400ppm is
used. The following conditions must be true in order for
this algorithm to run:
S The mode is occupied.
S Indoor Fan has been ON for at least 30 seconds.
S Indoor Air Quality sensor has a valid reading
As air quality within the space changes, the minimum
position of the economizer damper will be changed thus
allowing more or less outdoor air into the space depending
on the relationship of the indoor air quality to the
differential setpoint. If all the above conditions are true,
the IAQ algorithm will run and calculates an IAQ
minimum position value using a PID loop. The IAQ
minimum damper position is then compared against the
user configured economizer minimum position and the
greatest value becomes the final minimum damper
position of the economizer output.
Supply fan motor mounting
Supply fan motor adjustment plate
Motor pulley setscrew
Fan pulley setscrew
Blower wheel hub setscrew
Bearing locking collar setscrew
Compressor mounting bolts
Condenser fan motor mounting bolts
Condenser fan hub setscrew
If the calculated IAQ minimum position is greater than
the IAQ maximum damper position configuration then it
will be clamped to the configured value.
Demand Limit
If the RTU- - MP receives a level 1 (one degree offset), 2
(two degree offset), or a 3 (4 degree offset) to the BACnet
demand limit variable, the controller will expand the
heating and cooling setpoints by the configured demand
limit setpoint value and remain in effect until the BACnet
demand limit variable receives a 0 value.
See Table 25 for torque values.
Table 25 – Torque Values
120 ¦ 12 in ---lbs
120 ¦ 12 in ---lbs
72 ¦ 5 in ---lbs
72 ¦ 5 in ---lbs
72 ¦ 5 in ---lbs
65 to 70 in ---lbs
65 to 75 in ---lbs
20 ¦ 2 in ---lbs
84 ¦ 12 in ---lbs
71

FASTENER TORQUE VALUES

13.5 ¦ 1.4 Nm
13.5 ¦ 1.4 Nm
8.1 ¦ 0.6 Nm
8.1 ¦ 0.6 Nm
8.1 ¦ 0.6 Nm
7.3 to 7.9 Nm
7.3 to 7.9 Nm
2.3 ¦ 0.2 Nm
9.5 ¦ 1.4 Nm