Bryant 580J*08--14D Service And Maintenance Instructions page 55

(2-compressor) nominal 7.5 to 12.5 tons with puron (r-410a) refrigerant
Table of Contents

Advertisement

EXH
N1
Set
N
2V
10V
EXH
P1
P
Min
Pos
T1
Open
T
DCV
Max
2V
10V
AQ1
DCV
AQ
DCV
Set
SO+
2V
10V
SO
Free
SR+
Cool
B
C
SR
D
A
Fig. 71 - - EconoMi$er IV Control
Differential Enthalpy Control
For differential enthalpy control, the EconoMi$er IV
controller uses two enthalpy sensors (HH57AC078 and
CRENTDIF004A00), one in the outside air and one in the
return air duct. The EconoMi$er IV controller compares
the outdoor air enthalpy to the return air enthalpy to
determine EconoMi$er IV use. The controller selects the
lower enthalpy air (return or outdoor) for cooling. For
example, when the outdoor air has a lower enthalpy than
the return air, the EconoMi$er IV opens to bring in
outdoor air for free cooling.
Replace the standard outside air dry bulb temperature
sensor with the accessory enthalpy sensor in the same
mounting location. (See Fig. 60.) Mount the return air
enthalpy sensor in the return air duct. (See Fig. 69.)
Wiring is provided in the EconoMi$er IV wiring harness.
(See Fig. 62.) The outdoor enthalpy changeover setpoint is
set with the outdoor enthalpy setpoint potentiometer on
the EconoMi$er IV controller. When using this mode of
changeover
control,
turn
potentiometer fully clockwise to the D setting.
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation
control based on the level of CO
or return air duct.
There is both a factory-installed (FIOP) CO
(sensor 8001B with no display, which is mounted on the
side of the EconoMi$er) and a field-installed CO
(sensor 8002 with display, which is mounted on the return
air duct). While performing the same function, they differ
in their ability to be configured. The FIOP version is
preset and requires no changes in most applications. If a
configuration change is required, service kit #UIP2072
(software CD, cables, and instructions) and a laptop PC
are required. The field-installed version with display can
be configured stand-alone. (See section "CO
Configuration").
Mount
the
accessory
manufacturer specifications. The IAQ sensor should be
wired to the AQ and AQ1 terminals of the controller.
TR1
TR
24
24 Vac
Vac
COM
HOT
_
+
1
2
5
4
3
EF
EF1
C06038
the
enthalpy
setpoint
measured in the space
2
option
2
option
2
Sensor
2
IAQ
sensor
according
Adjust the DCV potentiometers to correspond to the DCV
voltage output of the indoor air quality sensor at the
user-determined setpoint. (See Fig. 72.)
CO SENSOR MAX RANGE SETTING
2
6000
5000
4000
3000
2000
1000
0
2
3
DAMPER VOLTAGE FOR MAX VENTILATION RATE
Fig. 72 - - CO
2
If a separate field-supplied transformer is used to power
the IAQ sensor, the sensor must not be grounded or the
EconoMi$er IV control board will be damaged.
When using demand ventilation, the minimum damper
position represents the minimum ventilation position for
VOC
(volatile
requirements. The maximum demand ventilation position
is used for fully occupied ventilation.
When demand ventilation control is not being used, the
minimum position potentiometer should be used to set the
occupied ventilation position. The maximum demand
ventilation position should be turned fully clockwise.
Exhaust Setpoint Adjustment
The exhaust setpoint will determine when the exhaust fan
runs based on damper position (if accessory power
exhaust is installed). The setpoint is modified with the
Exhaust Fan Setpoint (EXH SET) potentiometer. (See Fig.
66.) The setpoint represents the damper position above
which the exhaust fans will be turned on. When there is a
call for exhaust, the EconoMi$er IV controller provides a
45 ± 15 second delay before exhaust fan activation to
allow the dampers to open. This delay allows the damper
to reach the appropriate position to avoid unnecessary fan
overload.
Minimum Position Control
There is a minimum damper position potentiometer on the
EconoMi$er IV controller. (See Fig. 66.) The minimum
damper position maintains the minimum airflow into the
building during the occupied period.
When using demand ventilation, the minimum damper
position represents the minimum ventilation position for
VOC
(volatile
requirements. The maximum demand ventilation position
is used for fully occupied ventilation.
When demand ventilation control is not being used, the
minimum position potentiometer should be used to set the
occupied ventilation position. The maximum demand
to
ventilation position should be turned fully clockwise.
55
4
5
6
7
Sensor Maximum Range Settings
organic
compounds)
organic
compound)
800 ppm
900 ppm
1000 ppm
1100 ppm
8
C06039
ventilation
ventilation

Advertisement

Table of Contents
loading

This manual is also suitable for:

580j*08-14f

Table of Contents