Burner Ignition
Unit is equipped with a direct spark ignition 100% lockout
system. Integrated Gas Unit Controller (IGC) is located in
the control box. (See Fig. 37.) The IGC contains a
self- - diagnostic LED (light- - emitting diode). A single LED
on the IGC provides a visual display of operational or
sequential
problems
when
uninterrupted. (See Fig. 40.) When a break in power
occurs, the IGC will be reset (resulting in a loss of fault
history) and the indoor (evaporator) fan ON/OFF times
will be reset. The LED error code can be observed
through the viewport. During servicing refer to the label
on the control box cover or Table 9 for an explanation of
LED error code descriptions.
If lockout occurs, unit may be reset by interrupting power
supply to unit for at least 5 seconds.
125,000/90,000 BTUH INPUT
180,000/120,000 BTUH INPUT
240,000/180,000 BTUH INPUT
250,000/200,000 BTUH INPUT
Fig. 38 - - Spark Adjustment (08- - 14)
the
power
supply
is
Table 9 – LED Error Code Description*
LED INDICATION
ON
OFF
2 Flashes
3 Flashes
4 Flashes
4 Consecutive Limit Switch Faults
5 Flashes
6 Flashes
7 Flashes
8 Flashes
9 Flashes
LEGEND
LED --- Light Emitting Diode
* A 3 – second pause exists between LED error code flashes. If
more than one error code exists, all applicable codes will be
displayed in numerical sequence.
IMPORTANT: Refer to Troubleshooting Table 13 and 14
for additional information.
29
C08447
ERROR CODE
DESCRIPTION
Normal Operation
Hardware Failure
Limit Switch Fault
Flame Sense Fault
Ignition Lockout Fault
Induced --- Draft Motor Fault
Rollout Switch Fault
Internal Control Fault
Software Lockout

Advertisement