Supply Fan (Blower) Section - Bryant 580J*08--14D Service And Maintenance Instructions

(2-compressor) nominal 7.5 to 12.5 tons with puron (r-410a) refrigerant
Table of Contents

Advertisement

22 3/8 (569 mm)
DIVIDER
CLEANABLE
ALUMINUM
FILTER
BAROMETRIC
RELIEF
Fig. 3 - - Filter Installation
To remove the filter, open the spring clips. Re- - install the
filter by placing the frame in its track, then closing the
spring clips.
Manual Outside Air Hood Screen
This inlet screen is secured by a retainer angle across the
top edge of the hood. (See Fig. 4.)
Fig. 4 - - Screens Installed on Outdoor- - Air Hood
(Sizes 7-1/2 to 12-1/2 Tons Shown)
To remove the screen, loosen the screws in the top retainer
and slip the retainer up until the filter can be removed.
Re-install by placing the frame in its track, rotating the
retainer back down and tighten all screws.
OUTSIDE
AIR
HOOD
FILTER
FILTER
CAP
C08634
C07156

SUPPLY FAN (BLOWER) SECTION

WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on the fan system, shut off all unit power and tag- - out
the unit disconnect switch. Do not reach into the fan
section with power still applied to unit.
Supply Fan (Belt- -Drive)
The supply fan system consists of a forward- - curved
centrifugal blower wheel on a solid shaft with two
concentric type bearings, one on each side of the blower
housing. A fixed- - pitch driven pulley is attached to the fan
shaft and an adjustable- - pitch driver pulley is on the
motor. The pulleys are connected using a "V" type belt.
(See Fig. 5.)
Fig. 5 - - Belt Drive Motor Mounting
Belt
Check the belt condition and tension quarterly. Inspect the
belt for signs of cracking, fraying or glazing along the
inside surfaces. Check belt tension by using a spring-force
tool (such as Browning's Part Number "Belt Tension
Checker" or equivalent tool). Tension should be 6-lbs at a
5/8-in. (16 mm) deflection when measured at the
centerline of the belt span. This point is at the center of
the belt when measuring the distance between the motor
shaft and the blower shaft.
NOTE: Without the spring- - tension tool, place a straight
edge across the belt surface at the pulleys, then deflect the
belt at mid- - span using one finger to a 1/2-in. (13 mm)
deflection.
Adjust belt tension by loosening the motor mounting plate
front bolts and rear bolt and sliding the plate toward the
fan (to reduce tension) or away from fan (to increase
tension). Ensure the blower shaft and the motor shaft are
parallel to each other (pulleys aligned). Tighten all bolts
when finished.
4
C07087

Advertisement