Compressor Rotation; Cooling; Heating; Ventilation (Continuous Fan) - Bryant 551K 04N Series Service And Maintenance Instructions

Single package rooftop cooling only/electric heat unit with puron (r-410a) refrigerant 3 to 5 nominal tons
Table of Contents

Advertisement

Compressor Rotation

CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution can result in premature wear
and damage to equipment.
Scroll compressors can only compress refrigerant if rotat-
ing in the right direction. Reverse rotation for extended
times can result in internal damage to the compressor.
Scroll compressors are sealed units and cannot be repaired
on site location.
On 3-phase units with scroll compressors, it is important to be
certain compressor is rotating in the proper direction. To deter-
mine whether or not compressor is rotating in the proper direc-
tion:
1.
Connect service gages to suction and discharge pressure
fittings.
2.
Energize the compressor.
3.
The suction pressure should drop and the discharge pres-
sure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pressure
does not rise to normal levels:
4.
Note that the evaporator fan is probably also rotating in
the wrong direction.
5.
Turn off power to the unit and install lockout tag.
6.
Reverse any two of the unit power leads.
7.
Re-energize to the compressor. Check pressures.
The suction and discharge pressure levels should now move to
their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direction,
the unit will make an elevated level of noise and will not provide

cooling.

Cooling
Set space thermostat to OFF position. To start unit, turn on
main power supply. Set system selector switch at COOL posi-
tion and fan switch at AUTO. position. Adjust thermostat to a
setting below room temperature. Compressor starts on closure
of contactor.
Check unit charge. Refer to Refrigerant Charge section on
page 12.
Reset thermostat at a position above room temperature. Com-
pressor will shut off. Evaporator fan will shut off after a 30-
second delay.
To shut off unit, set system selector switch at OFF position.
Resetting thermostat at a position above room temperature
shuts unit off temporarily until space temperature exceeds ther-
mostat setting.

Heating

To start unit, turn on main power supply. Set system selector
switch to the HEAT position and set thermostat at a setting
above room temperature. Set fan to AUTO position.
First stage of thermostat energizes the first stage of the electric
heaters. Second stage of thermostat energizes the second stage
of electric heaters (if installed). Check heating effects at air
supply grille(s).
If electric heaters do not energize, reset limit switch (located on
supply-fan scroll) by pressing button located between termi-
nals on the switch.
To shut unit off, set system selector switch to the OFF position.
Resetting thermostat at a position below room temperature
temporarily shuts unit off until space temperature falls below
thermostat setting.

Ventilation (Continuous Fan)

Set fan and system selector switches at ON and OFF positions,
respectively. Evaporator fan operates continuously to provide
constant air circulation. When the evaporator-fan selector
switch is turned to the OFF position, there is a 30-second delay
before the fan turns off.

FASTENER TORQUE VALUES

Table 16 — Torque Values
Heat shield screws
Stator motor mounting screws 23 in.-lb (2.6 Nm) ±2 in.-lb (0.2 Nm)
Fan rotor mounting screws
Limit switch screws
Fan Deck bracket screws
Condenser fan motor
mounting screws
Condenser fan hub set screw
Compressor mounting bolts

START-UP, RTU OPEN CONTROLS

IMPORTANT: SET-UP INSTRUCTIONS
Installation, wiring and troubleshooting information for
the RTU Open Controller.: "582/559K, 581/551K Single
Package Rooftop Units with RTU Open Controls, Start-
up, Operation and Troubleshooting Instructions." Have a
copy of this manual available at unit start-up.
49
30 in.-lb (3.4 Nm) ±2 in.-lb (0.2 Nm)
23 in.-lb (2.6 Nm) ±2 in.-lb (0.2 Nm)
50 in.-lb (5.7 Nm) ±5 in.-lb (0.6 Nm)
50 in.-lb (5.7 Nm) ±5 in.-lb (0.6 Nm)
30 in.-lb (3.4 Nm) ±3 in.-lb (0.3 Nm)
60 in.-lb (6.8 Nm) ±5 in.-lb (0.6 Nm)
65 in.-lb (7.3 Nm) +10 in.-lb (1.2Nm)

Advertisement

Table of Contents
loading

Table of Contents