Bryant 580J*08--14D Service And Maintenance Instructions page 57

(2-compressor) nominal 7.5 to 12.5 tons with puron (r-410a) refrigerant
Table of Contents

Advertisement

The same equation can be used to determine the occupied
or maximum ventilation rate to the building. For example,
an output of 3.6 volts to the actuator provides a base
ventilation rate of 5% and an output of 6.7 volts provides
the maximum ventilation rate of 20% (or base plus 15 cfm
per person). Use Fig. 72 to determine the maximum
setting of the CO
sensor. For example, an 1100 ppm
2
setpoint relates to a 15 cfm per person design. Use the
1100 ppm curve on Fig. 72 to find the point when the CO
sensor output will be 6.7 volts. Line up the point on the
graph with the left side of the chart to determine that the
range configuration for the CO
ppm. The EconoMi$er IV controller will output the 6.7
volts from the CO
sensor to the actuator when the CO
2
concentration in the space is at 1100 ppm. The DCV
setpoint may be left at 2 volts since the CO
voltage will be ignored by the EconoMi$er IV controller
until it rises above the 3.6 volt setting of the minimum
position potentiometer.
SETTING
EQUIPMENT
1
Interface w/Standard
2
Building Control System
3
4
5
Economizer
6
7
8
Health & Safety
Parking/Air Intakes/
9
Loading Docks
2
sensor should be 1800
2
2
sensor
2
Table 23 – CO
Sensor Standard Settings
2
VENTILATION
OUTPUT
RATE
(cfm/Person)
Proportional
Any
Proportional
Any
Exponential
Any
Proportional
15
Proportional
20
Exponential
15
Exponential
20
Proportional
Proportional
Once the fully occupied damper position has been
determined, set the maximum damper demand control
ventilation potentiometer to this position. Do not set to the
maximum position as this can result in over-ventilation to
the space and potential high humidity levels.
CO
Sensor Configuration
2
The CO
sensor has preset standard voltage settings that
2
can be selected anytime after the sensor is powered up.
(See Table 23.)
Use setting 1 or 2 for Bryant equipment. (See Table 23.)
1. Press Clear and Mode buttons. Hold at least 5
seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
CO
2
ANALOG
CONTROL
OUTPUT
RANGE
(ppm)
0--- 10V
0--- 2000
4--- 20mA
2--- 10V
0--- 2000
7--- 20mA
0--- 10V
0--- 2000
4--- 20mA
0--- 10V
0--- 1100
4--- 20mA
0--- 10V
0--- 900
4--- 20mA
0--- 10V
0--- 1100
4--- 20mA
0--- 10V
0--- 900
4--- 20mA
0--- 10V
0--- 9999
4--- 20mA
0--- 10V
0--- 2000
4--- 20mA
57
OPTIONAL
RELAY
RELAY SETPOINT
HYSTERESIS
(ppm)
(ppm)
1000
50
1000
50
1100
50
1100
50
900
50
1100
50
900
50
5000
500
700
50